background image

Thank you very much for purchasing our LED lighting fittings.
Please read this instruction manual to use the product properly.

1) Prior to installing the fitting, check if the product is as per your order.
2) Check for a loose or damaged part due to an accident in transit, etc. 

Pipe Pendant Type, Bracket Type

1) Fix the terminal box and suspension hardware on the mounting surface firmly.
2) Screw the suspension pipes A and B into the fitting.
3) Put the fastening ring around the suspension pipe A and screw in the terminal box cover.

Confirm that the O ring is in the groove of the terminal box cover.

4) Raise the fitting and fit it to the suspension hardware.  Hook the suspension hook onto the terminal box.

Explosion proof type LED Lighting Fittings LZAB-V2

Performance

IP

rating

Hazardous Area

Usable in Zone 1 or Zone 2 hazardous areas where
there are hydrogen gases.

Type of Protection

Exde

ⅡB+H

2

T6X

After installing the product, be sure to hand this manual over to the user of the product. 

To be conserved

Rated Input Voltage

(Frequency)

IP 65

100-242 V AC

(50/60 Hz)

Prior to use

Inspection

Organization

TIIS

11E0000850G11

Instruction Manual

How to Install the Fitting

- 1 -

Содержание LZAB-V2

Страница 1: ...ion pipe A and screw in the terminal box cover Confirm that the O ring is in the groove of the terminal box cover 4 Raise the fitting and fit it to the suspension hardware Hook the suspension hook onto the terminal box Explosion proof type LED Lighting Fittings LZAB V2 Performance IP rating Hazardous Area Usable in Zone 1 or Zone 2 hazardous areas where there are hydrogen gases Type of Protection ...

Страница 2: ...ach other Loosen the reflector fixing screw and open the lamp house gently until it is supported by the chain The lamp house can be opened down to 90 degrees by removing the chain snap from the chain retainer Lead the applicable cable into the fitting through the cable gland and connect the power cable The white and red wires are power wires and the black wire is a grounding wire Pass the lead wir...

Страница 3: ...structure which is vibration free and less susceptible to damage Otherwise it might fall or be damaged The fastening bolts on the control unit chamber housing the control unit have a tensile strength level of A20 70 Don t remove the fastening bolts Removal of the bolts might cause a fire electric shock or explosion The product should be installed at an angle within the range from 0 oriented downwa...

Страница 4: ...e sure to ground For electrical connections use crimp type terminals etc to secure the connections and conduct insulation treatment An inadequate connection or inadequate insulation might cause an imperfect contact leading to an explosion fire or electric shock Be sure to turn off the power In grounding work be sure to follow the technical standards for electrical equipment and explosion protected...

Страница 5: ...abnormality immediately turn off the power switch Confirm that the abnormal condition has been eliminated and make a repair call Please note that the above addresses and phone numbers may be changed CAUTION 2 19 6 Yanagibashi Taito ku Tokyo 111 0052 Japan 81 3 5833 8971 For a product marked with a frequency don t use the product at a frequency other than 50 or 60 Hz local power supply frequency Us...

Отзывы: