Seifert 580320001 Скачать руководство пользователя страница 5

Version Nr. 1-5 - 13.06.2022

Doc. No. 99580320001

5 / 15

Programming
The operating parameters can be modified using the front keypad.  Access differs depending on the type of
parameter.  Access to configuration parameters is protected by a password that prevents unwanted
modifications or access by unauthorised persons.

Setting cooling set point, St1:

1. Press “SET” and display should show St1 and then the pre-set value of St1. (default: +35°C / +95°F)
2. Reach the desired value by using ▲ or ▼.
3. Press “SET” again to save the new value of St1.

Setting heating set point, St2 (only for units supplied with internal heater):

1. Press “SET” twice slowly and display should show St2 and then the pre-set value of St2. (default: +5°C /
+41°F)
2. Reach the desired value by using ▲ or ▼.
3. Press “SET” again to save the new value of St2.

​Setting temperature unit, low temperature alarm and high temperature alarm:

1. Press “PRG” button for 5 seconds to reach the modifiable parameter list.
2. Use ▲ or ▼ to reach the desired parameter:

C18 for temperature unit of measure
°C = 0
°F = 1
P25 for low temperature alarm threshold (default -10°C / +14°F)
P26 for high temperature alarm threshold (d55°C / +131°F)

3. Press “SET” on the desired parameter to display the current value.
4. Use ▲ or ▼ to reach the desired value.
5. Pressing “SET” temporarily saves the new value and returns to the parameters list.
6. Repeat steps 2-5 to set other parameters.
7. Press “PRG” for 5 seconds to permanently save the new values.

Содержание 580320001

Страница 1: ...3 4 Settings 4 5 Functional principle 7 6 Technical data 7 7 Performance graph 8 8 Mounting 9 9 Mounting Principle 10 10 Cut out dimensions 11 11 Dimensions H x W x D 12 12 Wiring diagram 13 13 Taking...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates e...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...plies to external ambient air as the coolant In air to air heat exchangers the internal temperature of the control cabinet cannot be cooler than the ambient temperature There are natural limits to the...

Страница 5: ...slowly and display should show St2 and then the pre set value of St2 default 5 C 41 F 2 Reach the desired value by using or 3 Press SET again to save the new value of St2 Setting temperature unit low...

Страница 6: ...ant Notes Whilst programming if no button is pressed for 10 seconds the display starts ashing and after 1 minute returns to the main display without saving changes To increase scrolling speed press an...

Страница 7: ...impeded Ambient air circuit 147 324 cfm Cabinet air circuit 150 324 cfm Mounting Wall mounted Housing Material Mild steel powder coated Dimension H x W x D 29 5 x 10 x 5 95 inch Weight 26 5 lbs Voltag...

Страница 8: ...Version Nr 1 5 13 06 2022 Doc No 99580320001 8 15 7 Performance graph...

Страница 9: ...absolute thoroughness to ensure that the unit works perfectly Transport damage check On delivery the carton containing the unit must be examined for signs of transport damage Any transport damage to...

Страница 10: ...Version Nr 1 5 13 06 2022 Doc No 99580320001 10 15 9 Mounting Principle 1 Heat exchanger 2 Mounting gasket 3 Slotted stud M6 x 1 inch 4 Enclosure 5 Washer A6 4 6 M6 Lock nut...

Страница 11: ...Version Nr 1 5 13 06 2022 Doc No 99580320001 11 15 10 Cut out dimensions...

Страница 12: ...Version Nr 1 5 13 06 2022 Doc No 99580320001 12 15 11 Dimensions H x W x D...

Страница 13: ...Version Nr 1 5 13 06 2022 Doc No 99580320001 13 15 12 Wiring diagram Power connector 1 L 2 N 3 PE 4 Alarm NO 5 Alarm COM 6 Alarm NC 7 Door contact 8 Door contact...

Страница 14: ...aintenance and cleaning must be carried out by specialists electricians The personnel must ensure that for the duration of this work the unit and the cabinet are disconnected from the electrical suppl...

Страница 15: ...packing The unit must be protected su ciently by shock absorbing padding hard foam corner pieces strips or cardboard corner pieces 17 Parts supplied Spare parts Accessories 1 x Heat exchanger 1 x Inst...

Отзывы: