Seifert 3BHB022684R0101 Скачать руководство пользователя страница 11

Version Nr. 1-1 - 05.03.2020

Doc. Nr. 9951650033

11 / 14

1 Red

5 VDC

Black #4

2 Black

0 VDC

Black #5

3 White

Hall

Black #6

4 not connected

Component lables

C1 - 4

Capacitor for fan

F1 - 4

Fan fuse 31.5 A (T)

LED D3/5/7/9

Fuse OK

LED D23/25/27/29

Fan OK - green

LED D24/26/28/30

Fan FAULT - red

Test buttons

0 - 10 sec

All fans ON

10 - 20 sec.

Fan 1 ON, fans 2,3,4 OFF

20 - 30 sec

Fans 1,2  ON, Fans 3,4 OFF

30 - 40 sec

Fans1,2,3 ON, Fan 4 OFF

40 - 120 sec

All fans OFF

S1 - 1-4 (ON) Fan selection
- 5 (ON) LT5165 selection

TEMP - Control set-point potentiometer
CB - Circuit breaker / protector 2-pole 6 A Type C

Содержание 3BHB022684R0101

Страница 1: ...3 Safety instructions 3 4 Technical functions 4 5 Technical data 4 6 Performance Graph 5 7 Mounting 6 8 Mounting Principle 7 9 Dimensions H x W x D 8 10 Electrical connection 9 11 Wiring diagram 10 12...

Страница 2: ...e instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...emperature sensitive components The characteristic graph shown in the section Performance graph applies to external ambient air as the coolant In air to air heat exchangers the internal temperature of...

Страница 5: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 5 14 6 Performance Graph T Temperature di erence between ambient and internal temperature P heat exchanger performance...

Страница 6: ...te thoroughness to ensure that the unit works perfectly Transport damage check On delivery the carton containing the unit must be examined for signs of transport damage Any transport damage to the car...

Страница 7: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 7 14 8 Mounting Principle...

Страница 8: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 8 14 9 Dimensions H x W x D...

Страница 9: ...er technical data Connecting the alarm and door contact interface To avoid unnecessary run time the heat exchanger can be switched on and o through the door contact There is also an alarm contact that...

Страница 10: ...ommon 3 Pink NC 4 not connected Connector J3 J5 J7 J9 Molex mini t jr 2 pole capacitor 1 Brown 2 Blue Connector J11 Molex KK 2 pole Door contact 1 Brown ON 2 Grey ON Connector J18 19 Molex mini t jr 2...

Страница 11: ...31 5 A T LED D3 5 7 9 Fuse OK LED D23 25 27 29 Fan OK green LED D24 26 28 30 Fan FAULT red Test buttons 0 10 sec All fans ON 10 20 sec Fan 1 ON fans 2 3 4 OFF 20 30 sec Fans 1 2 ON Fans 3 4 OFF 30 40...

Страница 12: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 12 14...

Страница 13: ...eaning must be carried out by specialists electricians The personnel must ensure that for the duration of this work the unit and the cabinet are disconnected from the electrical supply and protected a...

Страница 14: ...be maintained at all points between the unit and the external packing The unit must be rmly xed in the packing The unit must be protected su ciently by shock absorbing padding hard foam corner pieces...

Отзывы: