Version Nr. 1-1 - 05.03.2020

Doc. Nr. 9951650033

13 / 14

12. Taking into operation

As described before the unit is controlled in relation to the cabinet internal temperature. The required cabinet
temperature can be set on the potentiometer on the controller.The temperature adjustment range is between
0°C (left-hand stop) and 60°C (right-hand stop). The thermostat is pre-set at 35°C.

To adjust the cabinet internal temperature proceed as follows:

Remove the MCB access plate on the front of the unit.
Using a screw driver turn the adjustment wheel on the potentiometer “TEMP” slightly to the right (higher)
or to the left (lower).
Please note that the setting for the alarm signal should be at least 5 - 10°C higher than the setting for the
cabinet internal temperature.

Check that the new adjustment meets the necessary requirements. If necessary, repeat the procedure. Inspect
and if necessary replace the MCB access plate sealing tape.

13. Trouble shooting

In case of a fault logon to our website 

www.seifertsystems.com

 to locate your nearest servicing office or find

your nearest contact in the chapter “contacts” in this manual.

14. Maintenance & Cleaning

Danger from electrical voltage
Maintenance and cleaning must be carried out by specialists
(electricians). The personnel must ensure that for the duration of this
work the unit and the cabinet are disconnected from the electrical
supply and protected against unauthorised reactivation.

Danger through incorrect work on the unit.
The instructions in the cabinet manufacturer’s manual must be
adhered to!

Damage to the unit through incorrect maintenance and
repair! Maintenance and repair must be carried out by the
manufacturer or another specialist.

Fan replacement

The rated  life expectancy of the fan is L10 =30,000 hours under normal operating conditions.

To replace the internal or external fan, please proceed as following:

Remove the internal access panel by unscrewing the 10 fixing screws.
Disconnect the blower cables from the connectors.
Unscrew the four screws fixing the blower bracket to the cabinet.
Unscrew the fan from the bracket.
Re-assembly with the new blower is in reverse order.

Make sure that the blower cable length is the same as the one of the removed fan to ensure that the cable does
not come in contact with the blower while in operation. Make sure that the correct polarity is maintained.  (Refer
to circuit diagram).  Inspect and if necessary replace the internal access panel sealing tape. 
In addition the unit should have regular functional tests (approx. every 2,000 hours depending on the grade of
ambient pollution).

Содержание 3BHB022684R0101

Страница 1: ...3 Safety instructions 3 4 Technical functions 4 5 Technical data 4 6 Performance Graph 5 7 Mounting 6 8 Mounting Principle 7 9 Dimensions H x W x D 8 10 Electrical connection 9 11 Wiring diagram 10 12...

Страница 2: ...e instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...emperature sensitive components The characteristic graph shown in the section Performance graph applies to external ambient air as the coolant In air to air heat exchangers the internal temperature of...

Страница 5: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 5 14 6 Performance Graph T Temperature di erence between ambient and internal temperature P heat exchanger performance...

Страница 6: ...te thoroughness to ensure that the unit works perfectly Transport damage check On delivery the carton containing the unit must be examined for signs of transport damage Any transport damage to the car...

Страница 7: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 7 14 8 Mounting Principle...

Страница 8: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 8 14 9 Dimensions H x W x D...

Страница 9: ...er technical data Connecting the alarm and door contact interface To avoid unnecessary run time the heat exchanger can be switched on and o through the door contact There is also an alarm contact that...

Страница 10: ...ommon 3 Pink NC 4 not connected Connector J3 J5 J7 J9 Molex mini t jr 2 pole capacitor 1 Brown 2 Blue Connector J11 Molex KK 2 pole Door contact 1 Brown ON 2 Grey ON Connector J18 19 Molex mini t jr 2...

Страница 11: ...31 5 A T LED D3 5 7 9 Fuse OK LED D23 25 27 29 Fan OK green LED D24 26 28 30 Fan FAULT red Test buttons 0 10 sec All fans ON 10 20 sec Fan 1 ON fans 2 3 4 OFF 20 30 sec Fans 1 2 ON Fans 3 4 OFF 30 40...

Страница 12: ...Version Nr 1 1 05 03 2020 Doc Nr 9951650033 12 14...

Страница 13: ...eaning must be carried out by specialists electricians The personnel must ensure that for the duration of this work the unit and the cabinet are disconnected from the electrical supply and protected a...

Страница 14: ...be maintained at all points between the unit and the external packing The unit must be rmly xed in the packing The unit must be protected su ciently by shock absorbing padding hard foam corner pieces...

Отзывы: