background image

TB MRIK3  12.00 E

19

5.2

 

Setting procedure

After push button <SELECT/RESET> has been pressed,
always the next measuring value is indicated. Firstly the
operating measuring values are indicated and then the
setting parameters. By pressing the <ENTER> push but-
ton the setting values can directly be called up and
changed.

5.3

 

Systemparameter

5.3.1

 

Display of measuring values as

primary quantities (I

prim 

phase)

With this parameter it is possible to show the indication
as primary measuring value. For this purpose the pa-
rameter must be set to be equal with the rated primary
CT current. If the parameter is set to "sec", the measur-
ing value is shown as a multiple of the rated secondary
CT current.

Example:

The current transformer used is of 1500/5 A. The flow-
ing current is 1380 A. The parameter is set to 1500 A
and on the display "1380 A" are shown. If the parame-
ter is set to "sec", the value shown on the display is
"0.92" x In.

Note:

The pick-up value is set to a multiple of the rated secon-
dary CT current.

5.3.2

 

Display of earth current as primary

quantity (I

prim 

 earth)

The parameter of this function is to be set in the same
way as that described under 5.3.1. If the parameter is
not set to "sec", to relay types 

MRI3-X

 and 

MRI3-XR

 it

applies too, that the measuring value is shown as pri-
mary current in ampere. Apart from that the indication
refers to % of I

N

.

5.3.3

 

Nominal frequency

The adapted FFT-algorithm requires the nominal fre-
quency as a parameter for correct digital sampling and
filtering of the input currents.

By pressing <SELECT> the display shows "f=50" or
"f=60". The desired nominal frequency can be adjusted
by <+> or <-> and then stored with <ENTER>.

5.3.4

 

Display of the activation storage
(FLSH/NOFL)

If after an activation the existing current drops again be-
low the pickup value, e.g. I>, without a trip has been
initiated, LED I> signals that an activation has occured
by flashing fast. The LED keeps flashing until it is reset
again (push button <RESET>). Flashing can be sup-
pressed when the parameter is set to NOFL.

5.3.5

 

Parameterswitch/external
triggering of the fault recorder

By means of the parameter-change-over switches it is
possible to activate two different parameter sets. Switch-
ing over of the parameter sets can either be done by
means of software or via the external inputs RESET or
blocking input. Alternatively, the external inputs can be
used for Reset or blocking of the triggering of the fault
recorder.

Software-
parameter

Blocking input
used as

RESET input
used as

SET1

Blocking input

RESET input

SET2

Blocking input

RESET input

B_S2

Parameter switch

RESET input

R_S2

Blocking input

Parameter switch

B_FR

External triggering
of the fault re-
corder

RESET input

R_FR

Blocking input

External triggering
of the fault re-
corder

S2_FR

Parameter switch

External triggering
of the fault re-
corder

With the settings SET1 or SET2 the parameter set is ac-
tivated by software. Terminals C8/D8 and D8/E8 are
then available as external reset input or blocking input.

With the setting B_S2 the blocking input (D8, E8) is
used as parameter-set change-over switch. With the set-
ting R_S2 the reset input (D8, E8) is used as parameter-
set change-over switch. With the setting B_FR the fault
recorder is activated immediately by using the blocking
input. On the front plate the LED FR will then light up for
the duration of the recording. With the setting R_FR the
fault recorder is activated via the reset input. With the
setting S2_FR parameter set 2 can be activated via the
blocking input and/or the fault recorder via the reset in-
put.
The relevant function is then activated by applying the
auxiliary voltage to one of the external inputs.

Содержание MRIK3

Страница 1: ...MRIK3 Time overcurrent relay with auto reclosing relay...

Страница 2: ...1 Display 5 2 Setting procedure 5 3 Systemparameter 5 3 1 Display of measuring values as primary quantities Iprim phase 5 3 2 Display of earth current as primary quantity Iprim earth 5 3 3 Nominal fr...

Страница 3: ...ple of test circuit for MRIK3 relays 6 4 3 Checking the input circuits and measured values 6 4 4 Checking the operating and resetting values of the relay 6 4 5 Checking the relay operating time 6 4 6...

Страница 4: ...er sets selectable protective functions between definite time overcurrent relay or inverse time overcurrent relay selectable inverse time characteristics according to IEC 255 4 Normal Inverse Type A V...

Страница 5: ...TB MRIK3 12 00 E 5 3 Design 3 1 Connections Figure 3 1 Connections MRIK3 I Figure 3 2 Connections MRIK3 IE...

Страница 6: ...the C B auxiliary voltage at A5 is checked before a new auto reclosing takes place see also para 4 5 8 External blocking input A3 The unit is blocked when applying voltage to A3 Common point of the i...

Страница 7: ...ter the data have been read and deleted the re corder to ready again for further action Writing over If 1 3 or 7 recordings are chosen the relevant number of partial segments is reserved in the comple...

Страница 8: ...AR AR status CB Circuit breaker on RS Setting slave address 3 2 2 Setting LEDs P2 Two parameter sets I green pickup value phase current tI red trip delay time multiplier phase current I green pickup...

Страница 9: ...age The operating threshold of the signal inputs however has to be de fined by taking the supply voltage into account The fol lowing two different operating thresholds can be ad justed Low range tresh...

Страница 10: ...If a phase current exceeds the pickup value an alarm is given and after the set trip delay has elapsed the corresponding trip relay is activated The relay setting values for all parameters are stored...

Страница 11: ...gnment of the AR functions it is possible to activate or deactivate a Fast Trip func tion for each AR stage and for each protective function This is applicable for tripping before the 1 st AR up to tr...

Страница 12: ...atus transition to ready status when the auto reclos ing takes place status transition to blocked status by external or inter nal blocking The grey shaded sections indicate that no transition is possi...

Страница 13: ...tripping command until receiving of the C B check back signal 4 5 5 Unsuccessful reclosing After the start condition has been fulfilled the unit changes to starting status Now the dead time tD is star...

Страница 14: ...after an introduced reclosing The C B ready information is checked before an intro duced AR for further ARs There will be a reclosing when the circuit breaker ready had been given before the begin of...

Страница 15: ...uit is cleared After expiration of the dead time tD1 unit MRIK3 gives the reclosing command to the circuit breaker If the fault still exists the protection relay trips again and the above mentioned pr...

Страница 16: ...ulty lines Unit MRIK3 is in inactive status when the circuit breaker is switched off When the C B is manually closed the reclaim time is started In case there is a faulty line the C B is switched off...

Страница 17: ...st trip mode setting value in seconds setting value in seconds setting value in seconds 1ST ALL setting value in seconds 1ST LAST EXIT SELECT RESET one time for each value SHOT tF red tD1 tD2 tD3 tD4...

Страница 18: ...RESET I I Normal trip time TIME IE IE Fast trip FAST Running with tD1 tD2 tD3 tD4 Save parameter SAV ENTER Save parameter SAV ENTER for about 3 s Software version First part e g A00 Sec part e g 4 01...

Страница 19: ...the existing current drops again be low the pickup value e g I without a trip has been initiated LED I signals that an activation has occured by flashing fast The LED keeps flashing until it is reset...

Страница 20: ...CT push button the present time delay setting value is shown on the display The new setting value can then be changed by using push but tons If through a new setting another relay characteristic other...

Страница 21: ...ter 5 4 5 5 4 12 Trip delay for high set element of earth fault supervision tIE Similar to the chapter 5 4 6 5 4 13 Parameters auto reclosing Number of AR SHOTS Indicates how often the circuit breaker...

Страница 22: ...ping of the relay This protective function becomes only active after tripping and it is then checked whether all phase currents have dropped to 0 within time tCBFP Circuit Breaker Failure Protection S...

Страница 23: ...is initiated after a trip has occured A_PI After Pickup Storage is initiated after the last activation threshold was fallen short of TEST Storing is activated by simultaneous actuation of the keys and...

Страница 24: ...after the other After selection of the last blocking function renewed pressing of the SELECT RESET pushbutton switches to the assignment mode of the output relays Function Display LED Colour I Overcur...

Страница 25: ...ption MR Digital Multifunctional Relays have no function For relays without assignment mode this jump ers are used for parameter setting of alarm relays acti vation at pickup or tripping and manual re...

Страница 26: ...will store the altered value Actuation of the SELECT RESET key the protective functions are one after the other assigned to the first AR The following table shows all parameters that have to be set A...

Страница 27: ...t of the measuring values displayed The measuring values can optionally be shown in the display as a multiple of the sec rated value x ln or as primary current A According to this the units of the dis...

Страница 28: ...ck to a more recent fault data set At first FLT3 FLT2 FLT1 are al ways displayed When fault recording is indicated FLT1 etc the LEDs flash in compliance with the stored trip informa tion i e those LED...

Страница 29: ...set The software reset has the same effect as the SELECT RESET push button see also communica tion protocol of RS485 interface The display can only be reset when the pickup is not present anymore othe...

Страница 30: ...ion of the relay e g D01 By pressing the push button TRIP twice the display shows the second part of the software ver sion of the relay e g 1 00 The software version should be quoted in all correspond...

Страница 31: ...ls B7 B8 and the earth current input Compare the displayed current value with the reading of the amme ter The deviation must not exceed 3 of the measuring value or 1 IN By using an RMS metering instru...

Страница 32: ...t on other phases and earth current input circuits in the same manner Note Where test currents 4 x IN are used the thermal with stand capability of the current paths has to be consid ered see technica...

Страница 33: ...8 The display and LED indi cations should be reset immediately 6 4 11 Testing the external blocking with Block Trip function In order to simplify things the short circuit stage is to be tested here as...

Страница 34: ...ndicate that the relay is ready for auto reclosing Open the circuit breaker manually and check that the LED CB is extinguished immediately to indicate that the circuit breaker is not ready for auto re...

Страница 35: ...out to pickup ratio 97 Dropout to pickup ratio for phase current in range 0 2 x IN to 0 5 x IN 100 Returning time 30 ms Time lag error class index E 10 ms Minimum operating time 30 ms Transient overre...

Страница 36: ...s 0 05 s 0 1 s 0 2 s 3 from set value or min 1 IN 3 or 10 ms Table 7 1 Setting ranges for time overcurrent protection 7 3 2 Earth fault protection Setting range Step Tolerance Iprim SEK 0 002 50 kA 0...

Страница 37: ...0 02 1 Very Inverse Type B t I Is t I s 135 1 Extremely Inverse Type C t I Is t I s 80 2 1 Long Time Inverse s t 1 Is I 120 t I RI Inverse Time s t I I 236 0 339 0 1 t I S RXIDG characteristic s t I I...

Страница 38: ...910 20 I IS 0 1 1 10 100 1000 t s tI 0 05 0 1 0 2 0 3 0 4 0 6 0 8 1 0 1 4 2 0 3 0 4 0 6 0 8 0 10 0 Figure 7 2 Very Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 01 0 1 1 10 100 1000 t s tI 0 05 0 1 0 2 0 3 0...

Страница 39: ...5 0 4 0 3 0 2 0 1 0 05 Figure 7 5 Long Time Inverse 1 2 3 4 5 6 7 8 910 20 I IS 0 1 1 10 100 t s tI 8 0 6 0 3 0 4 0 2 0 1 6 1 0 1 4 1 2 10 0 0 8 0 6 0 5 0 4 0 3 0 2 0 1 0 05 Figure 7 6 RXIDG character...

Страница 40: ...ted by the C B OFF signal When this time has expired a C B defect is present Energy wait time 200 ms 10 ms During this time the C B stand by is supervised before re closing It can be deactivated by ap...

Страница 41: ...3 33 s 7 8 x 1 66 s 60 Hz FR Saving of the recording at the occurence P_UP TRIP A_PI TEST FR Pre trigger time 0 05 s 8 00 s Table 7 8 Parameters for the fault recorder is written over when a new trig...

Страница 42: ...th AR MRIK3 3 phase meauring I I I Rated current 1 A 5 A 1 5 Earth current measuring E Rated current in earth path 1 A 5 A 1 5 Housing 12TE 19 rack Flush mounting A D RS485 Alternatively with Modbus P...

Страница 43: ...tic overcurrent X X DEFT tI Overcurrent tripping delay s X X 0 03 I tRST Reset mode X X 0 s I Pickup value for high set element IN X X 0 5 tI Tripping delay for high set element s X X 0 03 IE Pickup v...

Страница 44: ...Set 2 Blocking the protection function PR_B PR_B PR_B Blocking the trip step TR_B Default setting Actual setting Function Blocking No blocking Blocking No blocking Parameter set Set 1 Set 2 Set 1 Set...

Страница 45: ...r the 1 st AR I TIME TIME I TIME TIME IE TIME TIME IE TIME TIME Activation of the 2 nd AR per I NO NO I YES YES IE NO NO IE NO NO Trip after the 2 nd AR I TIME TIME I TIME TIME IE TIME TIME IE TIME TI...

Страница 46: ...Blockage Input Default setting Actual setting Default setting Actual setting Low plugged X X High not plugged Code jumper Low High Range for Reset Input Low High Range for the CB OK Input Low high Be...

Отзывы: