36
TB MRIK3 12.00 E
7.3
Setting ranges and steps
7.3.1
Time overcurrent protection
Setting range
Step
Tolerance
Iprim
(SEK) 0.002...50 kA
0.001; 0.002; 0.005; 0.01; 0.02; 0.05;
0.1; 0.2
I>
tI>
0.2...4.0 x I
N
(EXIT)
0.03 – 260 s (EXIT)
(definite time)
0.05 - 10 (EXIT)
(inverse time)
0.01, 0.02, 0.05; 0.1 x I
N
0.01; 0.02; 0.1; 0.2; 0.5; 1.0; 2.0; 5.0
10.0; 20.0 s
0.01; 0.02; 0.05; 0.1; 0.2
±
3% from set value or
min.
±
1% I
N
±
3% or
±
10 ms
±
5% for NINV and VINV
±
7.5% for NINV and EINV
I>>
t
I>>
0,5...40 x IN (EXIT)
0.03...10 s (EXIT)
0.02; 0.05; 0.1; 0.2; 0.5; 1.0 x I
N
0.01 s; 0.02 s; 0.05 s; 0.1 s; 0.2 s
±
3% from set value or
min.
±
1% I
N
±
3% or
±
10 ms
Table 7.1: Setting ranges for time overcurrent protection
7.3.2
Earth fault protection
Setting range
Step
Tolerance
Iprim
(SEK) 0.002...50 kA
0.001; 0.002; 0.005; 0.01; 0.02; 0.05;
0.1; 0.2
I
E
>
t
IE
>
0.01...2.0 x I
N
(EXIT)
0.04 – 260 s (EXIT)
(definite time)
0.06 – 10 (EXIT)
(inverse time)
0.001; 0.002; 0.005; 0.01; 0.02;
0.05 x I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0; 2.0;
5.0; 10.0; 20.0 s
0.01; 0.02; 0.05; 0.1; 0.2
±
5% from set value or
±
0.3% I
N
±
3% or
±
15 ms
±
5% for NINV and VINV
±
7.5% for NINV and EINV
I
E
>>
I
IE
>>
0.01...15 x I
N
(EXIT)
0.04...10 s (EXIT)
0.01; 0.02; 0.05; 0.1; 0.2; 0.5 x I
N
0.01 s; 0.02 s; 0.05 s; 0.1 s; 0.2 s
±
5% from set value or min.
±
1% I
N
±
3% or
±
15 ms
Table 7.2: Setting ranges for earth fault protection