TB MRIK3 12.00 E
15
4.6
Time sequence diagrams of
MRIK3
Legend:
4.6.1
The unit is programmed for two shots, successful AR at the second shot
Figure 4.1: Two shots, second AR successful
In case of a short circuit an energizing follows with sub-
sequent tripping of the protection relay. The circuit
breaker is switched off and the short circuit is cleared.
After expiration of the dead time t
D1
unit
MRIK3
gives
the reclosing command to the circuit breaker.
If the fault still exists the protection relay trips again and
the above mentioned procedure is repeated as long un-
til either the fault was removed (here after the second
reclosing) or the number of the set SHOTs is reached.
4.6.2
The unit is programmed for two shots, unsuccessful AR
Figure 4.2: Two shots, AR unsuccessful
Here the time sequence as described in para. 4.6.1. The second reclosing shot is however unsuccessful.