TB MRD1-G 11.01 E
35
Key
D
isplay
Setting
Select
Setting range
(
•
no selection)
default
a
ctual
Set 1
S
et 2
S
et 3
S
et 4
minimun Reset time /latching time for relay 1
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 2
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 3
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 4
0.00 .... 1.00s /
exit
"
0.2 s
if
equipped
corresponding to relay 6 (If equipped)
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 7 (If equipped)
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 8 (If equipped)
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 9 (If equipped)
0.00 .... 1.00s /
exit
"
0.2 s
corresponding to relay 10 (If equipped)
0.00 .... 1.00s /
exit
"
0.2 s
Table: Reset time of the output relays
"
The reset time ist the minimum time the relay keeps energized after a trip. If the time is set to exit the output relay is con
figurated as a latching contact.
The relay keeps energized after a trip until the
MRD1
is RESETed. (DEVICE RESET)