7
Ver. 1.0
SHIN HWA Eng.Co.,Ltd.
CONTROL ACTUATOR
CA01H~CA120H
⑤
Adjustment of limit switch (LS1) for clock direction position control.
When dial gauge is positioned in 0%, please note
“Fig-5 Limit cam adjustment (Close)” use flat screw
driver, LS2P CAM should be rotated slightly into
arrow direction and matched until LS2 lamp is on.
⑥
Upon setting LS2P, signal control shall be
automatically matched.
⑦
Adjustment of limit switch (LS1) for counter-clock
direction position control.
When dial gauge is positioned in 100%, the “Fig-6.
Limit cam adjustment (Open)”, LS1P CAM should be
rotated slightly into arrow direction and matched
until LS2 lamp is on.
⑧
Upon setting LS1P, signal control shall be matched automatically.
⑨
After adjusting limit switch cam, tighten upon bolt and cam should be fixed into cam shaft.
Check the stop position by running the actuator electrically, and repeat the above process
if the stop position is incorrect
Torque limit switch
①
Do not operate randomly because it was adjusted when
dispatching our factory.
②
In standard mode, it is normal condition when rated
torque switch LSF lamp and LSR lamp are off.
How to adjust
LS1P
CAM
LS2P
CAM
Fig-6. Adjustment of limit cam (open)
Fig-7. Torque limit switch lamp
Fig-4. Adjustment process of
dial gauge
<Inside indicator for HAB Type>
How to adjust
LS1P CAM
LS2P CAM
Fig-5. Adjustment of limit cam (close)