6
Ver. 1.0
SHIN HWA Eng.Co.,Ltd.
CONTROL ACTUATOR
CA01H~CA120H
Caution for Installation of Control Actuator
①
Never give an impact on the output axis of the product. It is a slow equipment with the
total operation time of 30-60 seconds, but a momentary torque by shock makes a great
vibration and can give a damage to the gear, motor, or the like.
②
You must the axis lines of the output axis of the product and the corresponding axis parallel
and on the same line as much as possible.
If the axis lines are not parallel or not on the same line, a load can be applied to the output
axis of the product, causing a shorter life and a damage to a connecting link.
How to install control actuator
Fig.-2. How to install CA
Matters to check before operation
①
Check if the Control Actuator is firmly installed on the device to control.
②
Check if the damper or the valve smoothly operates. In addition, check if the subject to
control is completely opened or closed and if it receives an excessive pressure.
2-3 Limit switch adjustment (CA01H~CA10H FB, AB option type)
Position limit switch adjustment method (based on clock direction in view of output shaft)
①
Please note “Fig-1. CA structure” and check limit
switch position.
②
In “Fig-3. Limit switch and cam arrangement” upper
horse-shoe sensor LS2P is close sensor and below
horse-shoe sensor LS1P is open sensor.
③
Horse-shoe sensor LS1P and LS2P are available
position control and signal control respectively.
④
In order that dial gauge meet into 0% exactly, after
loosing
ⓐ
needle fixed bolt and adjust
ⓑ
needle
(Note Fig-4)
Fig-3. Limit switch and
cam arrangement