5
Ver. 1.0
SHIN HWA Eng.Co.,Ltd.
CONTROL ACTUATOR
CA01H~CA120H
2 Installation
2-1 Structure
When you maintain and check the Control Actuator, please refer to the below diagram.
Fig.-1. Control Actuator structure
2-2 Transport and Installation
Transport
When you transport this product, please avoid an accident such as fall and impact.
Place for Installation
- There is no special limit in the place for installation of the Control Actuator, but if it is exposed
to an environment with bad conditions for a long time, you had better use a proper protection
device.
- As well, you had better secure proper space around the Actuator for maintenance and repair.
Installation
- When you install the Control Actuator in a mounting place selected in advance for installation,
firmly fixate the Actuator with four bolts.
- Connect the lever arm and the corresponding lever.
- The operation angle is correctly adjusted before delivery, and you do not need to adjust it.
If you need to adjust it:
①
Give a current signal (a contact point signal in case of opening/closing control and angle
control) to put the Actuator in a complete opening (or closing) position.
②
Turn off the power supply, and separate the cover on the rear surface of the Actuator from
the main frame. Here, avoid giving a damage to the gasket.
③
Readjust the Position Limit Switch to fit the contact point.
(Refer to Clause 7 later for how to adjust the Limit Switch.)
④
Here, check if the needle of the indicator is in the complete opening (or closing) position
before adjusting.
⑤
Fit the gasket and the cover, close them, and tighten with a bolt.
- Please consult the manufacturer when changing the direction of rotation of the output shaft