Technical Data Sheet
FI 72.0239.0320E
Page 95 / 108
Checking outside of a cleaning cycle:
Outside a cleaning cycle, the input “dust emission” is monitored. If a dust emission is detected, a “general
dust emission” is generated.
Notes:
-
The dust emission detection is temporized (value of T19 time to adjust from 0 to 255 seconds
in the SELECT menu). Note : T19 is reset during the cleaning cycle.
-
The “general dust emission” fault is self-reset when there is no longer detected dust emission.
In fault visu mode, the fault is displayed as follows:
The red fault led on the front panel is associated to this fault.
Possibly an additional signaling can be included using relay outputs (see wiring diagrams).
Содержание SFX+NETWORK
Страница 21: ...Technical Data Sheet FI 72 0239 0320E Page 21 108 SIGNALLING...
Страница 22: ...Technical Data Sheet FI 72 0239 0320E Page 22 108 CONNECTIONS CONNECTION EXAMPLE...
Страница 24: ...Technical Data Sheet FI 72 0239 0320E Page 24 108 CONNECTIONS CONNECTION EXAMPLE...
Страница 26: ...Technical Data Sheet FI 72 0239 0320E Page 26 108 CONNECTIONS CONNECTION EXAMPLE...
Страница 28: ...Technical Data Sheet FI 72 0239 0320E Page 28 108 CONNECTIONS CONNECTION EXAMPLE...
Страница 31: ...Technical Data Sheet FI 72 0239 0320E Page 31 108 CONNECTIONS CONNECTION EXAMPLE...
Страница 34: ...Technical Data Sheet FI 72 0239 0320E Page 34 108 CONNECTIONS...
Страница 37: ...Technical Data Sheet FI 72 0239 0320E Page 37 108 SFX MODULE POWER CONSUMPTION...
Страница 38: ...Technical Data Sheet FI 72 0239 0320E Page 38 108...
Страница 85: ...Technical Data Sheet FI 72 0239 0320E Page 85 108...