10 

 |   

A = Fixed Sheave

B = Grub Screw

C = Adjustable Sheave

D = Locking Cap

E = Locking Cap Screw

ILL1208-D

The outer half of the pulley is on a thread and can be moved in 

or out by removing the locking cap and then turning the outer 

half by hand in the desired direction.

When an adjustment is made, replace the locking cap, aligning 

the screw hole with the nearest hole in the adjustable half. Lock 

it into place with the securing screw. Refit the belt, reset the belt 

tension, then run the cooler and check the amps. Repeat the 

process until the amp level is set.

You can start and stop the cooler for this procedure by using the 

isolating switch inside the cooler.

INSTALLATION

PULLEY ADJUSTMENT

The motor pulley is adjustable in order to set the motor amperes 

at the correct (nameplate) level, and thus provide the owner 

with full machine cooling capacity.

DO NOT USE THE PULLEY ADJUSTMENT TO SET BELT 

TENSION

The adjustment is made with the cooler switched OFF. Never 

attempt this procedure with the cooler operating.

• 

Remove the drive belt.

•  To increase the fan speed (and therefore the motor amps), 

the two halves of the pulley must be closer together, ie: turn 

the adjustable half clockwise.

•  To decrease the fan speed (and therefore the motor amps), 

the two halves of the pulley must be further apart, ie: turn the 

adjustable half counter-clockwise.

Important:

 Install all the pad frames except the one on the 

motor side.

Ensure that all intended doors, windows or other means of 

exhaust are open in the building, and that all outlet grilles are 

open fully.

WARNING:

 Beware of rotating fan, belt and pulleys whilst 

making adjustments to motor speed, pulley or belt tension 

settings. Ensure the cooler is switched OFF via the electronic 

module isolation switch whilst working inside the cooler.

Set the cooler running at the highest speed for about 10 

minutes, or until the motor has reached its normal operating 

temperature (hot!).Motor load must be checked without the 

pump running.

Clip your ammeter onto the free cable in the main termination 

box. This should be done by a trained licensed electrician.

MOTOR POWER (AMPS)

ILL1013-D

For convenience, the rated motor current, in amps, is printed 

on a small label attached near the cable fork (in addition to the 

normal motor nameplate label located at the back of the motor).
Check the measured amps against the motor nameplate amps. 

If the measured amps are less than the nameplate amps the 

adjustable motor pulley sheave must be altered to increase the 

fan speed, thereby delivering the full capability of the cooler to 

your installation. The measured amps must be equal or close 

to, but never more than the nameplate amps. (see heading 

“Pulley Adjustment”)
If the measured amps are greater than the motor nameplate 

amps the fan 

MUST

 be slowed down by adjusting the motor 

pulley sheave in the opposite manner. Failure to do this will 

cause overheating in the motor and may cause the motor’s 

thermal protector to trip.

Replace all covers when adjustments are completed using the 

screws provided.

Содержание BREEZAIR EXVQ

Страница 1: ... English INSTALLATION MANUAL EXVQ Evaporative Coolers ILL1672 A Original English Instructions ...

Страница 2: ...Connections 8 Coolers with Drain Valves 8 Installing the Inlet Solenoid 8 Fitting the Solenoid Cover 9 Installing the Drain Valve 9 Drain Valve Assembly 9 Connecting the MagIQtouch Controller 9 Motor Power Amps 10 Pulley Adjustment 10 Belt Tension 11 Motor Low Speed Setting 11 COMMISSIONING Test Operation 12 Diagnostic LED 12 Salinity LED 12 MagIQtouch Controller Information 12 Fault Codes 13 Sett...

Страница 3: ...ction s are necessary so the person doing the job does not injure themselves This should be considered in terms of What are the chances of an incident happening What could the possible consequence be What can you do to reduce or better still completely get rid of the risk SOME POINTS TO CONSIDER What is the best and safest access to the roof and working areas If a worker is alone who knows they ar...

Страница 4: ...EP 19 REFIT PAD FRAMES Refit the pad frames before testing the pump STEP 20 TEST PUMP Turn on the cooler and check the water is evenly distributed to all pads STEP 8 POWER CABLE Use the main power termination box for wiring connections inside cooler Terminate power cable outside of cooler in a junction box STEP 21 COOLER SETTINGS Where necessary adjust the cooler settings to suit customer requirem...

Страница 5: ...er and cooler owner s manual Explain maintenance requirements page 15 page 5 page 12 page 15 page 13 page 15 ON ILL3388 A STEP 4 LEVEL ROOF JACK Position level secure and seal the roof jack STEP 10 REGULATIONS Read adhere to the local national electrical and plumbing regulations STEP 5 CONVEY COOLER Convey the cooler to the roof Note Always use 2 people when handling manually STEP 11 INLET SOLENOI...

Страница 6: ...roximately the same length Carefully consider neighbouring residences and noise levels when locating the cooler if necessary talk to the customer and the neighbour before carrying out the installation Always locate the cooler where it will receive adequate fresh air and not in a recess where it may be starved for air or where the air is polluted Ensure location is a minimum of 10 3m from a solid f...

Страница 7: ...allation Use 24G or stronger metal roof jack The cooler may then be attached directly to the jack Replacement Installation Roof Jack recommended wall thickness should be 24G or stronger The supplied roof jack adaptor may be required to attach the cooler to the existing roof jack To assemble the roof jack adaptor hold panels at 90 degrees to one another Align slots in upper and lower panels then sl...

Страница 8: ...OCKED POSITION OPERATING POSITION INSTALLATION SECURING THE LEG SUPPORTS The telescopic leg supports with feet attached slide up and down inside the four corner posts By removing the screw from the lower end of the corner post you enable the leg support to slide down to roof level ILL958 A ILL958 A Make sure each leg is vertical before securing Secure foot to roof with 2 screws minimum ILL959 B Ma...

Страница 9: ...an reservoir Seal the gap between the conduit and the knock out hole with silicone sealant after making connections and clamping the conduit cable Important Ensure that all electrical connections are tight Loose connections will cause overheating that may lead to machine damage or fire Replace all covers on completion of work using only the screws supplied Do not tamper with factory wiring Before ...

Страница 10: ... Flexible hose assembly G Solenoid cover H Solenoid power leads In cooler I Float Valve Nipple BSP J BSP to 1 4 Compression Fitting or BSP Nut Olive ILL1228 E SIA2008 ILL1228 E SIA INSTALLING THE INLET SOLENOID For coolers fitted with a drain and solenoid valve it is a requirement to fit the new detachable hose set as supplied Any old hose sets should not be re used For EXVQ model coolers fit the ...

Страница 11: ...ling the controller Coolers are supplied with a 66 20m control cable Longer cable lengths are available from Seeley Important The maximum cable length allowed from the MagIQtouch controller to the first cooler is 82 25m For any additional coolers added into the system with a link module the maximum allowed length is 131 40m Therefore failure of the product or components to operate correctly due to...

Страница 12: ...sure that all intended doors windows or other means of exhaust are open in the building and that all outlet grilles are open fully WARNING Beware of rotating fan belt and pulleys whilst making adjustments to motor speed pulley or belt tension settings Ensure the cooler is switched OFF via the electronic module isolation switch whilst working inside the cooler Set the cooler running at the highest ...

Страница 13: ... normal circumstances However some adjustment may be necessary to suit specific installations After you have set the motor amps and belt tension correctly check the speed variation of the cooler When the control is changed from maximum to minimum settings there should be an easily recognizable difference in fan speed If there is not check the following That windows and doors are open Rule of thumb...

Страница 14: ...immersed in water Water not detected The probes are immersed in water but are open circuit or measured salinity is less than 20µs cm the water has very little salt content Continuously on No water in Pan WaterMiser Drain Valve option is active SALINITY LED The bottom LED is red only and displays salinity setting information ILL1641 A ILL1823 A MAGIQTOUCH CONTROLLER INFORMATION Diagnosis and cooler...

Страница 15: ...level set too low For Breezair coolers the water level should be set to 13 64 5mm above the float valve base Ensure probe plug is properly connected Plug connections at electronic module are upside down or misaligned Water too pure for the probes to sense water is present Pressure build up in pipes can lock up the solenoid valve when a non return isolation valve is used in the water supply line It...

Страница 16: ...al Drain Turns cooler off and drains the pan reservoir Pad Flush Turns cooler off and runs pump for a specified amount of time Drain And Dry Cooler will drain and fan will run for 1 hour every day at a specified time Water Manager Select the preferred water management method Salinity Measurement replaces water when Salinity level reaches set point Timed Drain drains pan reservoir After 8 pan fill ...

Страница 17: ...d can open and close without interference PLUMBING FLUSHED The water pipes were flushed of any foreign materials before connection to cooler was made NO EXTERNAL LEAKS The water is connected with no leaks at fittings NO INTERNAL LEAKS Check all internal water hoses are securely fitted to water distribution spreaders and other internal fittings SECURE Water pipes are correctly saddled as per plumbi...

Страница 18: ...t condition via the tri colour LED on cooler electronics box Rectify fault as indicated and restart the cooler MagIQtouch Controller failure Replace MagIQtouch Controller Pump runs but no water circulation Pump runs but pads lack water Insufficient water in pan Reservoir Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insufficient water...

Страница 19: ......

Страница 20: ... 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD UNIT 11 BYRON BUSINESS CENTRE DUKE STREET HUCKNALL NOTTINGHAM NG15 7HP UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1002 S 56TH AVENUE SUITE 101 PHOENIX ARIZONA 85043 USA SEELEY INTERNATIONAL AFRICA PTY LTD 6 WITTON ROAD FOUNDERSVIEW SOUTH MODDERFONTEIN 1609 GAUTENG SOUTH AFRICA EXVQ Cooler Installa...

Отзывы: