DU/SD SERIES INSTALL OPERATION MAINTENANCE MANUAL
|
47
APPENDIX E1 - LEAVING AIR TEMP EXCEEDS 40°C
HCV12 with an airflow of 840 L/s over the heat exchanger to achieve a 28°C rise in temperature. The outside air
temperature is 15°C. Thermostat is set to 29°C .
As the leaving air temperature is greater than 40°C the unit will shut down. To stop the unit from shutting down the
dampers need to be opened further to allow for greater airflow across the heat exchanger.
APPENDIX E2 - SET TEMPERATURE CANNOT BE REACHED
HCV12 with an airflow of 2098 L/s over the heat exchanger to achieve a 11°C rise in temperature. The outside air
temperature is 15°C. Thermostat is set to 29°C.
The airflow over the heat exchanger is too high to allow for the temperature to increase sufficiently to heat the room to
the set temperature.
APPENDIX E: TEMPERATURE RISE OVER
HEAT EXCHANGER
AMI094-A
AMI095-A
Figure 29: Leaving Air Exceeds 40C
Figure 30: Set Temperature Not Reached