![SEELEY INTERNATIONAL AIRA DU SD Series Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/seeley-international/aira-du-sd-series/aira-du-sd-series_installation-and-operation-manual_1233142030.webp)
28
|
All units have two high limit controls per heat exchanger. The following steps are to be completed during the
commissioning of the unit.
1. Check that the high limit control is securely installed and free from damage.
2.
Confirm that the high temperature limit is as per client specification. Confirm that the control is wired into the control
box.
3.
Using a digital thermometer and heat gun confirm that the switch activates at the required temperature. Record
Results.
4.5.2 Thermostat and User Controls
Check that the thermostat and wall switch are installed and wired back to the unit.
If a BMS is installed refer to Aira Manual AM006 for wiring information.
COMMISSIONING INFORMATION
AMI088-A
4.5.3 RLU Screens
The modulating valve screen indicates the percentage
valve opening. If the valve is positioned less than 10%
the burner will turn off. If the Position is greater than 20%
the burner will turn on.
The room set temperature is indicated by the RH value.
As the room thermostat set value is altered the value will
change accordingly. The LH value is the current room
temperature as room thermostat. The RLU has an upper
limit setting of 29 Deg C.
The leaving air temperature sensor is indicated by the
LH value. The leaving air temperature sensor is located
on the outlet of the unit. The value indicates the current
ambient temperature in the ductwork. The RH value is
a calculated minimum set temperature value and is not
used so can be ignored.
The following steps are to be completed.
1. Turn on power to the unit.
2. Check the thermostat set temperature against RLU read out. Test against the entire range of the thermostat.
3.
Using a digital thermometer record the temperature and confirm that the leaving air sensor and RLU read out
matches.
Figure
24
: RLU Screens
Содержание AIRA DU SD Series
Страница 1: ...INSTALLATION AND OPERATION DU SD SERIES HEATER OR MODELS Original English Instructions AMI115 A ...
Страница 2: ......
Страница 4: ...2 ...