background image

MR-2602 Installation & Operator’s Manual

14

Figure 15: Connecting the Alarm and Trouble Relays

Figure 16: Connecting Optional Devices

See installation sheets for the remote devices for 
detailed wiring and address setup.

1. Maximum of 4 MR-2605-T per panel.
2. Maximum of 4 MR-2605-AT per panel.

Secur-bus Wiring Chart

Current 

(mA)*

22-awg Wire

18-awg Wire

16-awg Wire

14-awg Wire

ft

ft

ft

m

ft

m

ft

m

15

2,524

769

6,410

1,954

10,160

3,098

16,000

4,878

30

1,262

384

3,200

976

5,080

1,549

8,000

2,439

45

842

256

2,135

651

3,385

1,032

5,340

1,628

60

631

192

1,600

488

2,540

774

4,000

1,220

75

505

154

1,280

390

2,030

619

3,200

976

90

421

128

1,065

325

1,690

515

2,670

814

105

361

110

915

279

1,450

442

2,285

697

120

315

96

800

244

1,270

387

2,000

610

135

281

86

710

216

1,125

343

1,780

543

150

252

77

640

195

1,015

309

1,600

488

165

229

70

580

177

920

280

1,455

444

180

210

64

530

162

845

258

1,335

407

195

194

59

490

149

780

238

1,230

375

210

180

55

455

139

725

221

1,145

349

225

168

51

425

130

675

206

1,065

325

*See module current ratings chart for current drawn by each module attached to the secur-
bus.

Содержание MR-2602

Страница 1: ...LT 2015 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be read carefully M R 2 6 0 2 Fire Alarm Control Unit ...

Страница 2: ......

Страница 3: ...ifications 10 4 2 Connecting NAC Devices Class A and Class B 12 5 0 Panel Operation 16 5 1 Operating Sequences 16 5 2 General Zone Fire Alarms 16 5 3 Waterflow Alarms 16 5 4 Supervisory Zone Alarms 17 5 5 Trouble Operation 17 5 6 System Reset Operation 19 5 7 Lamp Test 19 5 8 Walk Test Installer function only 20 5 9 NAC operation 21 5 10 Relay Function 21 6 0 Programming the MR 2602 System 22 6 1 ...

Страница 4: ...tor s Manual ii 9 0 Appendix Table of Compatible Smoke Detectors 33 9 1 Smoke Detector Bases 35 9 2 Compatible 4 Wire Smoke Detectors 35 9 3 Compatible Horns Strobes 36 FCC Compliance Statement 38 Warranty Warning Information 39 ...

Страница 5: ...imensions 9 Figure 7 Knockout Locations 9 Figure 8 MR 2602 Terminal Descriptions 10 Figure 9 Connecting 2 Wire Alarm Initiating Devices 11 Figure 10 Connecting 4 Wire Smoke Detectors 12 Figure 11 Connecting NAC Devices Class B 12 Figure 12 Connecting NAC Devices Class A 12 Figure 13 Connecting Batteries 13 Figure 14 Connecting AC Power 13 Figure 15 Connecting the Alarm and Trouble Relays 14 Figure...

Страница 6: ......

Страница 7: ...ire Alarm Systems Information provided with this unit is intended as a guide Installation of this equipment optional system components alarm initiating devices and notification appliances must follow the manufacturer s guidelines as contained in their respective installation documents all applicable codes and the instructions of the Local Authority Having Jurisdiction General Installation requirem...

Страница 8: ...er damage or extended power outages has occurred 1 5 Standby Power The MR 2602 provides standby battery support for lead acid rechargeable batteries The required capacity of the standby batteries must be calculated using the charts and tables within this manual for the period as required by national or local codes and standards Even though the calculation table within this manual includes a safety...

Страница 9: ...s Programmable using the MR 2644 handheld programmer Mounts inside the enclosure and connects to the main panel using a supplied 4 wire cable with connector MR 2644 Programmer Handheld programmer for the MR 2806 DACT MR 2605 T Remote trouble indicator Single gang plate complete with common trouble buzzer trouble visual indicator AC on visual indicator and a trouble silence lamp test switch Mounts ...

Страница 10: ...ank insert Zone designations can be written directly on the insert or can be created using Word for Windows printed on Avery label 5167 and applied to the insert CPU FAULT Figure 1 MR 2602 cabinet with door closed Note Use Security Screw SPAENAUR 381 064 provided to meet UL 864 Rev 9 requirement Figure 2 MR 2602 display and controls Figure 3 MR 2602 Cabinet Overview Figure 4 Zone Label Insert ...

Страница 11: ... gauge and wire run distances for the connected components initiating devices indicating devices and secur bus connected components Review the programming section of this manual and determine the operating characteristics required of the initiating zones indicating zones and common panel features 2 5 Electrical Specifications Note This system should be installed and serviced by qualified fire alar...

Страница 12: ... totals in the standby and alarm columns 5 Add up all the current drawn from the AUX output in the standby and alarm mode and put those totals in the standby and alarm columns 6 Add up all the currents in the standby column and the Alarm column 7 Convert the standby and alarm currents from mA to Amps divide mA by 1000 8 Write in the standby time required 24 or 60 Hr 9 Multiply the standby Amps tim...

Страница 13: ...60 x MR 2605 R3 Standby 0 x Alarm 24 x 5 AUX Standby x Alarm x 6 Total standby and alarm current mA mA 7 Divide standby mA and alarm mA by 1000 Amp Amp 8 Select standby time required 24 or 60 Hr Hr 9 Standby Amp Hr multiply 8 7 Amps Hr Amp Hr 10 Select alarm time required 0 08 or 0 5 Hr 11 Alarm Amp Hr multiply 7 10 Amps Hr Amp Hr 12 Total Amp Hr standby Amp Hr 9 alarm Amp Hr 11 Amp Hr 13 Multiply...

Страница 14: ...g temperature 32 F to 122 F 0 C to 50 C Humidity 95 RH non condensing Close to a source of unswitched AC power 3 2 Panel Assembly and Modules Locations The panel comes completely assembled from the factory Remove the lower dead front for access to the battery compartment Remove display control panel for access to AC connections Figure 5 Panel Assembly and Modules Locations 240V 50Hz 120V 60Hz GND ...

Страница 15: ...MR 2602 Installation Operator s Manual 9 3 3 Mounting the MR 2602 Figure 6 Mounting Dimensions Figure 7 Knockout Locations Dimensions in inches ...

Страница 16: ...P P ripple power limited Aux power shorts must be restored by removing all Aux Power loading COM Auxiliary common power return unswitched 24 VDC 500 mA max SCOM Auxiliary common power return switched open circuit on system reset or on 4 wire smoke detector reset 24 VDC 500 mA max Please refer to Appendix A for compatible 4 wire smoke detectors DAT Data line for remote module communications CLK Clo...

Страница 17: ...n the de energized state Contacts are rated 30 VDC 2 Amps max Z1 Zone 1 positive input Z1 Zone 1 negative input Zone output is 24 VDC nominal to power 2 wire smoke detectors Maximum current draw is 60 mA in alarm and is limited by the zone circuitry Zones may be configured to monitor both 2 wire smoke detectors and initiating devices that employ dry contacts manual stations heat detectors Z2 Same ...

Страница 18: ...al loop wire resistance is 100 ohms Zone Wiring Chart 4 2 Connecting NAC Devices Class A and Class B Figure 11 Connecting NAC Devices Class B Figure 12 Connecting NAC Devices Class A Wire Gauge Distance feet Distance meters 18 7 690 2 345 Maximum loop resistance is 100 ohms Maximum current in alarm is 60 mA 16 12 195 3 717 14 19 230 5 861 ...

Страница 19: ...49 769 235 1 250 381 2 70 0 75 205 63 325 99 513 156 833 254 2 00 1 00 154 47 244 74 385 117 625 191 1 60 1 25 123 38 195 59 308 94 500 152 1 30 1 50 103 31 163 50 256 78 417 127 Note This chart is based on a minimum source voltage of 22 volts and a maximum line loss of 2 volts thus leaving a minimum of 20 volts at the last notification appliance 240V 50Hz 120V 60Hz GND N Primary AC Note The wire ...

Страница 20: ... 262 384 3 200 976 5 080 1 549 8 000 2 439 45 842 256 2 135 651 3 385 1 032 5 340 1 628 60 631 192 1 600 488 2 540 774 4 000 1 220 75 505 154 1 280 390 2 030 619 3 200 976 90 421 128 1 065 325 1 690 515 2 670 814 105 361 110 915 279 1 450 442 2 285 697 120 315 96 800 244 1 270 387 2 000 610 135 281 86 710 216 1 125 343 1 780 543 150 252 77 640 195 1 015 309 1 600 488 165 229 70 580 177 920 280 1 4...

Страница 21: ...cted to the Secur bus All devices are supervised See section for adding and deleting devices on the Secur bus Remix 1 25 ohms Immix Amps Distance Remix 1 000 feet 2 wire resistance in ohms per 1 000 feet Note Shielded wire has a much higher capacitance value and distances are severely reduced Devices Description MR 2605 T External to control panel Up to 4 of each device may be connected MR 2605 AT...

Страница 22: ...ns out see Automatic Signal Silence on page 25 If the automatic silence timer is enabled the panel will automatically silence the NACs 30 minutes after the last fire alarm Each zone alarm will restart the timer giving a full 30 minutes after the last alarm before the NACs are silenced Once the NACs are silenced the signals silenced LED turns on and any flashing zone alarm LEDs turn on steady The c...

Страница 23: ...uble and it goes into alarm the zone trouble LED is extinguished until that zone is restored and the panel has been reset The common trouble LED will remain on steady until all supervisory alarms have been restored and the panel reset All other common trouble indicators will operate normally Supervisory Fire Alarm Priority The supervisory zone LED the common supervisory LED and the buzzer in the s...

Страница 24: ...urns on Ground on extended conductor turns on sounds second on off deactivates Ground LED turns on AC fails completely or is low for more than 10 seconds brownout turns on sounds second on off deactivates AC LED turns off Installer Programming Mode Active flashes sounds second on off deactivates AC LED turns off Loss of Remote Trouble Unit turns on sounds second on off deactivates Loss of Remote A...

Страница 25: ...ne or more zones is still in alarm after the reset period the panel will activate the NACs as programmed If there are no alarms but one or more Supervisory zones is still off normal after the reset period the panel will sound the trouble buzzer in the Supervisory mode If there are no alarms or supervisory conditions but a trouble is present in the panel after the reset period the panel will sound ...

Страница 26: ...y remote connection is not activated 3 To return the system to normal operation press the Walk Test button If you do not press the Walk Test button the system will return to normal operation after one hour If any zones are in alarm at the end of the walk test the zones will indicate silenced signals Type of activation LEDs NACs Trouble Buzzer Fire Alarm or Fire Supervisory Zone alarm Supv LED turn...

Страница 27: ... if all zone fire alarms are restored Only NAC2 can be set in this mode Class A operation selections If the panel NACs are set for class A operation then there is only one NAC In this configuration the NAC output can only be set for steady or temporal using the NAC1 programming options For class A the NAC2 Strobe option is not available 5 10 Relay Function Alarm Relay The panel activates the alarm...

Страница 28: ...PCB as shown below Figure 17 Locating the Walk Test Switch 2 Press and hold the Walk Test Switch for two seconds The common trouble buzzer and common trouble LED turn on and pulse second on off 3 Press any button The trouble buzzer is silent and the zone 1 alarm LED turns on steady The common trouble LED continues to flash 4 The panel is now ready to program Programming the Panel The control panel...

Страница 29: ...l move to the next programming section when you press the Silence Trouble button Example in the Zone 1 programming sub section pressing Silence Alarm will scroll through each zone type setting null zone instant zone auto verify zone etc When the panel shows the zone type you want for zone 1 press Silence Trouble to move on to Zone 2 programming Exiting the Programming Mode When you come to the end...

Страница 30: ...rm condition Zone type 03 Waterflow zone This zone type is intended for waterflow alarm initiating contact devices only Do not mix other alarm initiating devices on this zone For Waterflow delay use actuating devices with a built in delay of 30 seconds or more The overall maximum waterflow alarm initiation delay allowed is 90 seconds NFPA A 5 6 2 1996 edition When the contact on a Waterflow alarm ...

Страница 31: ...LED on steady Automatic Signal Silence If Automatic Signal Silence is enabled 30 minutes after the last fire alarm on the system the panel restores the NACs to normal alarms are silenced If another alarm occurs after the NACs are silenced the panel will restart the timer for another 30 minute period If Automatic Signal Silence is disabled the panel will not silence the NACs automatically NAC2 Stro...

Страница 32: ... be either audible or silent If the One Man Walk Test is set for audible then the following will occur On a fire or Supervisory alarm restoral the bells will pulse ONCE On a zone or system trouble restoral except ground fault the bells will pulse TWICE On any ground fault restoral the bells will pulse THREE times If the One Man Walk Test is set for silent the bells will not sound during the walk t...

Страница 33: ...on Programming All common trouble LEDs flashing To Enter this Programming Section 1 Enter the installer programming mode section 0 2 Press and hold the System Reset button for 2 seconds The Z1 ALM LED and TRB LED will be ON and all the System Trouble LEDs will flash To Remove Module Physically remove the module from the system and enter the reset section programming as described above Press the Si...

Страница 34: ...ule Fault Restore Flashing NAC1 Trouble LED NAC 1 Trouble Steady NAC1 Trouble LED NAC 1 Trouble Restore Flashing NAC2 Trouble LED NAC 2 Trouble Steady NAC2 Trouble LED NAC 2 Trouble Restore Flashing Battery Trouble LED Battery Trouble Steady Battery Trouble LED Battery Trouble Restore Flashing Ground Fault LED Ground Fault Trouble Steady Ground Fault LED Ground Fault Restore Flashing Signal Silenc...

Страница 35: ...properly and if it is it may take up to 24 hours to recharge the batteries Once the battery is charged the battery fault LED will go OFF 7 3 Default Operation On first power up all programmable features will be in the default mode Do a Lamp Test to verify that all the indicators function It is suggested that an initial verification of operation be done before the panel is programmed Verify that ea...

Страница 36: ...ough the settings for each programming section e g to change the zone type or to turn an option on or off 4 Press Silence Trouble to move to the next programming section e g to move from zone 1 to zone 2 5 The panel will indicate the current programming section using the Common Trouble LEDs as shown below Please see 6 2 Programming Section Descriptions on page 24 for detailed descriptions of each ...

Страница 37: ...ing Section 1 NAC1 LED on steady on page 25 Factory default 8 4 NAC Auto silence Strobe Programming Section 2 Please see NAC Auto silence and Strobe Programming Section 2 NAC2 LED on steady on page 25 Factory default ZONE ALARM LED On Zone No Type 00 05 Label 1 1 2 2 ZONE ALARM LED On Programming Section Settings 1 NAC1 Temporal Steady Temporal Steady 2 NAC2 Temporal Steady Temporal Steady ZONE AL...

Страница 38: ...lease see Waterflow Programming Section 4 Ground Fault LED on steady on page 26 Factory default 8 7 50 60 Hz Option Section 5 Factory default ZONE ALARM LED On Programming Section Settings 1 Signal Silence Inhibit Timer Enabled Disabled 2 One Man Walk Test Audible Silent ZONE ALARM LED On Programming Section Settings 1 Silencing of Waterflow Alarms Enabled Disabled ZONE ALARM LED On Programming Se...

Страница 39: ... with Thermal 2 wire 12 24VDC 01 25 System Sensor 2400AT A N A N A Photoelectric with Thermal and Horn 2 wire 24VDC 01 25 System Sensor 2400AIT A N A N A Photoelectric with isolated Thermal and Horn 2 wire 24VDC 01 25 System Sensor 2451 A B401 B401B DH400 N A Plug in Photoelectric type smoke detector 01 25 System Sensor 2451TH A B401 B401B N A Plug in Photoelectric type smoke detector with Thermal...

Страница 40: ... B401 B401B DH400 N A Plug in Low Profile Ion 01 25 System Sensor 2151 2151A A B401 B401B DH400 N A Plug in Low Profile Photo 01 25 System Sensor 2100S A N A N A 2 wire direct wire Photoelectric 01 25 System Sensor 2100TS A N A N A 2 wire direct wire Photoelectric Thermal 01 30 System Sensor 2100AT A N A N A 2 wire direct wire Photoelectric Audible Thermal 01 30 System Sensor 2100TR A N A N A 2 wi...

Страница 41: ...stem Sensor B116LP N A 2 wire base 24VDC form contact 25 System Sensor DH400 N A Duct Detector Mount 25 System Sensor RMK400 N A Recessed mount kit for Series 400 Manufacture r Models System Sensor 1124B 2124B 2124TB 2124S 2124TS 2124R 2124TR 2124AT 2124ATR 2124AITR 1424 2424 2424TH 2424AT 1151 2151 2424AIT 6424 1451 2451 22451TH Detector with B112LP Base Detector with B402B Base Detection Systems...

Страница 42: ... S 75 20 30 S24110 W A S 110 20 30 H24 W A H 20 30 MDL W A Module 20 30 No suffix Red suffix W White suffix A Canadian version Gentex Type Cd Voltage FWR GEH24 H 20 31 GES24 15 S 15 20 31 GES24 15 75 S 15 75 20 31 GES24 30 S 30 20 31 GES24 60 S 60 20 31 GES24 75 S 75 20 31 GES24 110 S 110 20 31 GEC24 15 H S 15 20 31 GEC24 15 75 H S 15 75 20 31 GEC24 30 H S 30 20 31 GEC24 60 H S 60 20 31 GEC24 75 H...

Страница 43: ...W FR W H S 75 20 31 NS4 24110W FR W H S 110 20 31 NS 2 wire NS4 4 wire AS 2415W FR W S 15 20 31 AS 241575W FR W S 15 75 20 31 AS 2430W FR W S 30 20 31 AS 2475W FR W S 75 20 31 AS 24110W FR W S 110 20 31 AS4 2415C FR W S 15 20 31 AS4 2430C FR W S 30 20 31 AS4 2475C FR W S 75 20 31 AS4 24110C FR W S 110 20 31 AH 24 R H 20 31 AH 24 WP R H 20 31 MT 24 R H 20 31 MT4 24 R H 20 31 MT 24 SL VFR H S 15 20 ...

Страница 44: ...r there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Increase the separation between the equi...

Страница 45: ...ondition and installed correctly If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a fire alarm system After a power interruption has occurred immediately conduct a complete system test to e...

Страница 46: ...ed or awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or busy for certain periods of time...

Страница 47: ... suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any other abuse mishandling or improper application of the products Warranty Procedure To obtain service under this warranty please return the item s in question to the point of purchase All authorize...

Страница 48: ...e replacement product will be charged for each replacement unit WARNING Secutron Inc recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not limited to criminal tampering or electrical disruption it is possible for this product to fail to perform as expected NOTE Under no circumstances shall Secutron Inc be liable for any specia...

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ...8 Cheektowaga New York 14227 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any language or computer language in any form by any means electronic magnetic optical chemical manual or otherwise without the prior consent of Secutron ...

Отзывы: