MR-2602 Installation & Operator’s Manual
13
NAC Wiring Chart
Figure 13: Connecting Batteries
Figure 14: Connecting AC Power
Maximu
m Total
Loop
(ohms)
Maximu
m
Current
(A)
18-Awg
Wire
16-Awg
Wire
14-Awg
Wire
12-Awg
Wire
ft
m
ft
m
ft
m
ft
m
8.00
0.25
615
188
978
297
1,538
469
2,500
762
5.00
0.50
308
94
488
149
769
235
1,250
381
2.70
0.75
205
63
325
99
513
156
833
254
2.00
1.00
154
47
244
74
385
117
625
191
1.60
1.25
123
38
195
59
308
94
500
152
1.30
1.50
103
31
163
50
256
78
417
127
Note:
This chart is based on a minimum source voltage of 22 volts and a maximum line loss
of 2 volts thus leaving a minimum of 20 volts at the last notification appliance.
240V 50Hz
120V 60Hz
GND
N
Primary AC
Note: The wire gauges must be
no less then the size required by
the Canadian Electrical Code
C22.1, Part 1, Section 32.