MR-2602 Installation & Operator’s Manual
22
6.0 Programming the MR-2602
System
6.1 How to Program the MR-2602
You can program the panel using the controls and indicator LEDs. There are no DIP switches to set for
programming.
Once programmed, the operating modes selected are maintained in non-volatile memory that will retain the
programmed information even if all power is removed from the panel.
Entering the Programming mode
1. Remove the lower front cover and locate the ‘Walk Test Switch’ behind the control panel PCB, as shown
below.
Figure 17: Locating the Walk Test Switch
2. Press and hold the Walk Test Switch for two seconds. The common trouble buzzer and common trouble
LED turn on and pulse ½ second on/off.
3. Press any button. The trouble buzzer is silent, and the zone 1 alarm LED turns on steady. The common
trouble LED continues to flash.
4. The panel is now ready to program.
Programming the Panel
The control panel has six different programming sections, which are shown in the table below. The Panel
Status LEDs indicate which programming section you are currently in.
Note:
All zone alarms must be reset prior to entering the programming mode. While the panel is in
programming mode, the annunciators will show a trouble condition.