DIP Switch Settings

4

DIP Switch Settings

Each annunciator needs to be assigned a unique, sequential address via DIP switches SW1-1, SW1-2, and 
SW1-3. DIP switch SW1-4 is used to allow disabling of some front panel slide switches.

Set the annunciator address (see the manual for the fire alarm control panel being used), as follows in the 
table below:

Annunciators on a common RS-485 connection must be numbered sequentially; i.e.: 1,2,3,4, and not 
randomly such as 5,3,7. Note that not all annunciator “addresses” are valid for all fire alarm control panels. 
Refer to the fire alarm control panel manual for further information.

Jumper Selection

Jumper JP1 connects pins 2 and 3 and thus provides an eight bit checksum.

JW4

Jumper Intact = Buzzer silence & Lamp Test local function only. System Reset & Signal Silence are 
disabled.

Cut Jumper to have all remote functions operate.

SW1-1

= Address 

A0\

>

Three digit address of the annunciator (address 
range 1 to 7 inclusive)

SW1-2

= Address 

A1

SW1-3

= Address 

A2/

SW1-4 = 

When SW1-4 is “off”, the System Reset and Signal Silence slide-switches are 
always disabled, regardless of the operation of the keyswitch. The Buzzer 
Silence and Lamp Test slide-switches will operate with the use of the 
keyswitch.

When SW1-4 is “on”, all four slide -switches on the front panel will operate 
with the use of the keyswitch. 

Annunciator 

Address

SW1 DIP Switch Settings

SW1-1

SW1-2

SW1-3

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

Содержание MR-2312-AT

Страница 1: ...58SEC WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be read...

Страница 2: ......

Страница 3: ...s and Displays 2 Wiring Instructions 3 DIP Switch Settings 4 Jumper Selection 4 Specifications and Features 5 Enclosure 5 Electrical Specifications 5 Current Drain for Battery Calculations 5 Warranty...

Страница 4: ......

Страница 5: ...by a keyswitch Each circuit indicator is a bi colour LED that is automatically configured to match the fire alarm control panel configuration Technical Support For all technical support inquiries plea...

Страница 6: ...s Indicating and relay circuits are not remotely displayed For more details refer to the manual of the fire alarm control panel that the annunciator will be connected to The MR 2312 AT has a keyswitch...

Страница 7: ...imum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP power limited cable WARNING Accidentally connecting any of the 24 VDC wires to...

Страница 8: ...Jumper JP1 connects pins 2 and 3 and thus provides an eight bit checksum JW4 Jumper Intact Buzzer silence Lamp Test local function only System Reset Signal Silence are disabled Cut Jumper to have all...

Страница 9: ...to 16 points Not expandable Standby 35 mA Max All LED s illuminated 140 mA max Current Drain for Battery Calculations The lamp test feature draws the maximum normal current because it illuminates all...

Страница 10: ...installed correctly If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often ac...

Страница 11: ...rted or awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notifi...

Страница 12: ...beyond the control of Secutron Inc such as excessive voltage mechanical shock or water damage damage caused by unauthorized attachment alterations modifications or foreign objects damage caused by per...

Страница 13: ...e which Secutron Inc has predetermined and which may be revised from time to time will be charged for each unit repaired Products which Secutron Inc determines not to be repairable will be replaced by...

Страница 14: ...Warranty Warning Information 10...

Страница 15: ...MR 2312 AT Remote Annunciator Wiring and Instruction Manual 11...

Страница 16: ...Cheektowaga New York 14227 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any lan...

Отзывы: