Страница 1: ...58SEC WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be read...

Страница 2: ......

Страница 3: ...s and Displays 2 Wiring Instructions 3 DIP Switch Settings 4 Jumper Selection 4 Specifications and Features 5 Enclosure 5 Electrical Specifications 5 Current Drain for Battery Calculations 5 Warranty...

Страница 4: ......

Страница 5: ...by a keyswitch Each circuit indicator is a bi colour LED that is automatically configured to match the fire alarm control panel configuration Technical Support For all technical support inquiries plea...

Страница 6: ...s Indicating and relay circuits are not remotely displayed For more details refer to the manual of the fire alarm control panel that the annunciator will be connected to The MR 2312 AT has a keyswitch...

Страница 7: ...imum current for all annunciators summed together Note All circuits are power limited and must use type FPL FPLR or FPLP power limited cable WARNING Accidentally connecting any of the 24 VDC wires to...

Страница 8: ...Jumper JP1 connects pins 2 and 3 and thus provides an eight bit checksum JW4 Jumper Intact Buzzer silence Lamp Test local function only System Reset Signal Silence are disabled Cut Jumper to have all...

Страница 9: ...to 16 points Not expandable Standby 35 mA Max All LED s illuminated 140 mA max Current Drain for Battery Calculations The lamp test feature draws the maximum normal current because it illuminates all...

Страница 10: ...installed correctly If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often ac...

Страница 11: ...rted or awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notifi...

Страница 12: ...beyond the control of Secutron Inc such as excessive voltage mechanical shock or water damage damage caused by unauthorized attachment alterations modifications or foreign objects damage caused by per...

Страница 13: ...e which Secutron Inc has predetermined and which may be revised from time to time will be charged for each unit repaired Products which Secutron Inc determines not to be repairable will be replaced by...

Страница 14: ...Warranty Warning Information 10...

Страница 15: ...MR 2312 AT Remote Annunciator Wiring and Instruction Manual 11...

Страница 16: ...Cheektowaga New York 14227 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any lan...