Introduction

4

Dip Switch Settings

Each annunciator needs to be assigned a unique, sequential address via DIP switches SW1-1, SW1-2, and SW1-3. 
DIP switch SW1-4 is used to allow disabling of some front panel slide switches.

Set the annunciator address (see the manual for the fire alarm control panel being used), as follows in the table 
below

Jumper Selection

Jumper JP1 connects pins 1 and 2 and thus provides an eight bit checksum. The eight bit checksum is used for MR-
2300 Series Panel. 

JW4 (Orange Wire)

Jumper Intact = Buzzer silence & Lamp Test local function only. System Reset & Signal Silence are disabled.

Cut Jumper (Orange Wire) to have all remote functions operate.

SW1-1

= Address 

A0

>

Three digit address of the annunciator (address 
range 1 to 7 inclusive)

SW1-2

=  

Address 

A1

SW1-3

=  

Address 

A2

SW1-4 = 

When SW1-4 is “off”, the System Reset and Signal Silence slide-switches are 
always disabled, regardless of the operation of the keyswitch. The Buzzer 
Silence and Lamp Test slide-switches will operate with the use of the 
keyswitch.

When SW1-4 is “on”, all four slide -switches on the front panel will operate 
with the use of the keyswitch.

Annunciator 

Address

SW1 DIP Switch Settings

SW1-1

SW1-2

SW1-3

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

Notes: 

Annunciators on a common RS-485 connection must be numbered sequentially; i.e.: 1,2,3,4, and not 

randomly such as 5,3,7!! Note that not all Annunciator “Addresses” are valid for all Fire Alarm Control Panels. 
Refer to the Fire Alarm Control Panel Manual for further information.

Содержание MR-2306-AT

Страница 1: ...T 648SEC WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be r...

Страница 2: ......

Страница 3: ...ction 2 Controls Displays 2 Wiring Instruction 3 Dip Switch Settings 4 Jumper Selection 4 Specifications Features 5 Enclosure 5 Electrical Specifications 5 Current Drain for Battery Calculations 5 War...

Страница 4: ......

Страница 5: ...yswitch Each Circuit Indicator is a bi colour LED that is automatically configured to match the Fire Alarm Control Panel configuration Technical Support For all technical support inquiries please cont...

Страница 6: ...er Silence Lamp Test 8 Circuit Status LED s Notes The MR 2306 AT is supplied with NP 386 paper labels for zone identification This annunciator displays initiating circuit status only no individual cir...

Страница 7: ...field wiring needs to be of an appropriate gauge for the number of annunciators and the total wiring run length See the specifications section Current Drain for Battery Calculations and calculate the...

Страница 8: ...ess A0 Three digit address of the annunciator address range 1 to 7 inclusive SW1 2 Address A1 SW1 3 Address A2 SW1 4 When SW1 4 is off the System Reset and Signal Silence slide switches are always dis...

Страница 9: ...e Annunciation of up to 8 Points Not Expandable Standby 35 mA Max All LED s On 90 mA Max Current Drain for Battery Calculations The maximum normal current drain will be during Lamp Test when all lamps...

Страница 10: ...operative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a fire alarm system After a power i...

Страница 11: ...reos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telephone Lines If telephone...

Страница 12: ...ble installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arising out of any ot...

Страница 13: ...product will be charged for each replacement unit WARNING Secutron Inc recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to but not li...

Страница 14: ......

Страница 15: ......

Страница 16: ...Niagara Falls New York 14305 Tel 888 SECUTRON 888 732 8876 Fax 905 660 4113 No part of this publication may be reproduced transmitted transcribed stored in a retrieval system or translated into any la...

Отзывы: