MR-23006-AT Remote Multiplex Annunciator Panel Wiring and Installation Manual
5
Specifications & Features
Enclosure
A standard 4-gang Electrical Box is used.
Electrical Specifications
•
24 VDC nominal voltage
•
Slide-Switch Controls, LED indicators, and Keyswitch to enable Controls.
•
Local Buzzer, Indicators (AC-On, Common Trouble, Signal Silence), and Controls
(System Reset, Lamp Test, Buzzer Silence, Signal Silence).
•
Annunciation of up to 8 Points.
•
Not Expandable.
•
Standby: 35 mA Max., All LED’s “On”: 90 mA Max.
Current Drain for Battery Calculations
The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a
time. Thus the currents are as follows:
The
Normal Standby Current
is used for Battery Size Calculations (see the Fire Alarm Control Panel manual) and
includes the current drain for the Trouble Buzzer, Trouble LED, and one Alarm LED. The
Maximum Current
is
used to calculate the wire size (see the
Wiring Instruction
).
Normal Standby Current
= 35 mA
Maximum Current
= 140 mA