34
4.6
CHIMNEY CHASE AND MULTIPLE TERMINATIONS
For the purpose of this manual, a chimney chase is considered a part of the chimney
system rather than part of a building. The termination must be placed a minimum of 18"
(460 mm) above the chase.
For installations where more than one chimney is located in the same chase or within the
same area, we suggest that their terminations be separated by at least 16" (410 mm)
horizontally, and 18" (460 mm) vertically. This separation is to prevent smoke
migrating from one chimney to another (see figure 34).
Figure 34
4.7
CHIMNEY ADAPTOR
(Secure Temp
S2100+
/
Nova Temp
/
The fireplace is normally supplied
with a chimney adaptor suitable for
the Secure Temp
ASHT+
/ Nova
Temp
chimney. If you want to
install a Secure Temp
S-2100+
/ Nova
Temp
chimney, an adaptor is
available (6UCA) (figure 35). A
separate starter section will also be
required if AC chimney is installed.
Figure 35