3.6 Setting the door opening time
4 0 # Default value, the door opening time is 50 milliseconds.
4 (1-98) # the door opening time is 1-98 seconds. The default is 5 seconds
4 99 # Set the keypad to switch mode, that is, change the lock status every time once door
opened
For example, set the door opening time to 5 seconds: 4,5#.
Note: The 50-millisecond door opening time is suitable for the electric control lock or the access
control special power supply. The switch mode is suitable for the normally open normally closed
door.
3.7 Set the alarm time
5 0 # default , No alarm
5 1-3 # alarm time is 1-3 minutes
Eg. Set the alarm time for 1 minute: 51#
3.8 set the door contact
6 0 # default , door contact invalid
6 1 # door contact valid
Eg. Set the safe mode in lock mode : 61#
There are two functions if connect with door contact by default:
1. The door left open in 10 seconds after opening, the built-in buzzer will ring. Close the door ,
swipe the valid card or input correct user PIN Code #, wait for more than 1 minutes will release
alarm.
2. If the door was opened by force, or open the door after 120 seconds when normal unlock. The
outer connecting alarm and built-in buzzer will alarm simultaneously. swipe the valid card or input
correct user PIN Code #, wait for more than 1 minutes will release alarm.
3.9 Setting the security mode
7 0 # Default value, set to normal mode
7 1 # Set to lock mode. When the invalid card, user password or administrator password is
continuously tried 10 times, the keypad will be automatically locked for 10 minutes.
7 2 # Alarm mode. If there are continuously 10 invalid cards, 10 incorrect PIN number or
administrator code within 10 minutes, both the buzzer and alarm output will be operated. Swiping
valid card, or input valid PIN number, or wait for 1 minute will release the alarm output.
For example, set to lock mode: 71#
3.10 Exit from the administrator mode
In the administrator mode, press * key several times, until the indicator light is red(constantly).