Seametrics FT430 Скачать руководство пользователя страница 14

FT430/440/450 INSTRUCTIONS

Seametrics • 253.872.0284 

Page 14 seametrics.com

INP 

View or change the filter (set F), jitter (set J), enable REED 

mode  (50Hz  maximum  pulse  input)  and  enable  BURST 

mode.  Use  the  filter  setting  if  the  display  is  jumping 

excessively due to flow conditions. Use the jitter setting to 

enter a time delay to handle start up conditions. Jitter units 

are seconds. Turn the BURST mode on if the input pulses 

to the FT unit are not delivered steadily across time but 

are delivered in groups or 'bursts' of pulses separated by 

moments of inactivity.

PCODE 

Enter the pass code for access to protected features.

Protected Features

To enter the protected features use the left/right arrow 

keys to navigate to the Pcode tab, found in the secondary 

menu. Press the enter key and then enter the pass code. 

The protected menu, shown below, will now be displayed. 

The tabs have the following functions:

Set CD

  Enter a user created numerical pass code.

Lock

 

Lock menu functions to prevent unauthorized 

changes.

E/D R

  Disable or enable the total volume reset 

function.

PCNT

  Keeps a running tally of the number of times 

the pass code has been used.

OUTP

MAIN

INP

P CODE

EXIT

PRESS    TO SET F, J, REED

AND PULSE INDICATOR

A secondary menu is available with further options. Enter 

the secondary menu by pressing the up arrow four times 

while EXIT is highlighted. 

OUTP 

View or change the function of Out P tab on the main menu.
The FT440 has two available alarm outputs while the FT430 

and FT450 only have one.  The P/A tab changes the function 

of the scaled pulse outputs. Default is scaled pulse. Any 

scaled pulse output can be changed to alarm high or alarm 

low. If alarm options are selected menu tabs for setting the 

alarms will be displayed on the main menu (alarm 1) or the 

secondary menu (alarm 2) If the alarm options are selected 

a Set H (hysteresis) tab is available. The hysteresis entry is 

a % value. The value defines the % change required  for a 

change in alarm state to occur.
The factory setting will show Set P2 (FT440 only) which 

allows one to view or change the volume of flow totalized 

per pulse sent to pulse out 2. The units for Set P2 follow 

the units selected for the rate display. If P2 is selected 

as an alarm the menus will change to Set A2 and a Set 

H (hysteresis) tab is available. The hysteresis entry is a 

%  value.  The  value  defines  the  %  change  required  for  a 

change in alarm state to occur.

Set 4 (FT440 only) input the flow rate at which 4 mA (min) 

output is desired.

ADJ L (FT440 only) allows the adjustment of the 4 mA and 

20 mA values so that one can tune performance of the 

FT440 to match the installed system values. The adjustment 

units range from 0-32. Positive values adjust the setting 

incrementally larger and negative values adjust the setting 

incrementally lower.

OUTP

MAIN

INP

P CODE

EXIT

SCROLL TO SELECT A 

SUBMENU AND CHANGE

FEATURES

OUTP

MAIN

INP

P CODE

EXIT

PRESS    TO SET ALARMS,

PULSE OUT, AND 4-20  mA

Secondary Menu Functions

To conserve battery life on battery powered 

units, the display screen goes to a blank screen 

after approximately 3 minutes of non-use. 

Push any button to reactivate display.

SETTINGS

OUTP

MAIN

INP

P CODE

EXIT

PRESS    TO SET PASSCODE 

AND CHANGE PROTECTED 

FEATURES

Содержание FT430

Страница 1: ...PROUDLY MADE IN THE USA C e rtified Compa n y ISO ISO 9001 FT430 440 450 FT430 440 450 Rate Total Indicator Rate Total Indicator Instructions Instructions Optional Protective Cover Closed...

Страница 2: ...3 Wire Mechanical Meter Page 8 Connections for FT430 139 or FT440 139 115Vac Option Page 9 FT440 3 wire Mechanical Dual Scaled Pulse Output Page 9 FT440 EX Magmeter Page 10 FT440 139 EX Magmeter Page...

Страница 3: ...the loop and sensors requiring more power than the loop can supply Pulse and 4 20mA analog outputs can be used to signal external devices e g certain metering pumps and water treatment controls Alter...

Страница 4: ...Mega Liters Day Million Gallons Day Fluid Oz Second Minute Hour Day Barrels Second Minute Hour Day Total Units Gallon Gallon x 1000 Liters Mega Liter Cubic Meter Acre Feet Cubic Feet Cubic Feet x 100...

Страница 5: ...h or Low YES High or Low YES High or Low PULSE OUTPUT 2 SCALED FT430 FT440 Note 2 FT450 TYPE Not Available Current sinking Not Available MAX VOLTAGE 36 Vdc MAX CURRENT 100 mA MAX FREQUENCY 6 5 Hz PULS...

Страница 6: ...sing to the depression on the top of the flow sensor 5 Using an ordinary screwdriver inserted in one side of the slot see drawing tighten the screw as much as possible 6 Strip the wire ends make the c...

Страница 7: ...installed on the cord grip and must be snugly tightened on the cable or on a plug that would take the place of the cable Plugs with flanges are to be installed from the outside of the compression nut...

Страница 8: ...ER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ RED WHITE BLACK Micropower Flow Sensor FT450 Pulse Pass thru Pulse Responsive Metering Pump Current Sinking Polarity Sensitive Lithium C 3Vdc Replaceab...

Страница 9: ...40 139 115Vac Option POWER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ RED WHITE BLACK _ 9 30 Vdc Loop Power Supply Flow Sensor FT440 Electronic Metering Pumps _ S _ _ _ 4 20mA Device _ GROUND Conne...

Страница 10: ...orward Output Power M ax6m A 30Vdc 12 24Vdc _ _ White Green Red Black POWER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ FT440 GREEN WHITE BLACK _ FT440 139 Dual Power Supply Lower Housing 4 20mA Dev...

Страница 11: ...TION DIAGRAMS FT4XX Sensus Tranceiver Connections FT4XX Eqipped with Sensus Board Side View Sensus Tranceiver Red Power Clock Black Ground Green Data Red Black Green NOTE A Sensus 2m 6 ft output cable...

Страница 12: ...ry gallon of flow Note that the decimal is fixed at three places If you only have two decimal places for your K factor enter a zero for the third digit If unable to set K factor the unit is locked to...

Страница 13: ...quals Set P R UNIT SET K T UNIT SET D SET P RESET EXIT TOTAL GALLONS PRESS TO SET UNITS FOR DISPLAY R UNIT SET K T UNIT SET D SET P RESET EXIT 000 PRESS TO CHOOSE NUMBER OF DECIMAL PLACES IN TOTAL DIS...

Страница 14: ...he P A tab changes the function of the scaled pulse outputs Default is scaled pulse Any scaled pulse output can be changed to alarm high or alarm low If alarm options are selected menu tabs for settin...

Страница 15: ...se output Wrong pulse output setting Use Set P to correct pulse output setting Polarity reversed on pulse output terminals Reverse leads Display reads normally but no or incorrect 4 20mA output FT440...

Страница 16: ...roducts or parts that are typically consumed during normal operation ix Use of parts or supplies other than those sold by Seametrics which cause damage to the products or cause abnormally frequent ser...

Отзывы: