Changing Flow Indicator Settings

THE HOME SCREEN

The  HOME  Screen,  shown  above,  is  the  normal  screen 

which displays TOTAL flow volume and flow RATE. The Four 

buttons below the LCD display are used to access menu 

screens for viewing and changing setup parameters.

0.00

0

GPD

MID

SETTINGS

Menu Navigation

           
The left/right keys are used to move through the menus 

and position the cursor during data entry. The up arrow is 

used to scroll through the available values that are to be 

entered. (examples: numerical values for K factor entry or 

selection of units from the available options) The enter key 

(represented on the keypad by the check mark) is used to 

save selected entries and in conjunction with the exit tab to 

move between menu screens.  As one navigates the menus 

the current parameter setting is shown and instructions are 

displayed for how to change the selected parameter.

MAIN MENU

All menu screens consist of two rows of tabs surrounding a 

dialog box that lets you view and change setup parameters. 

SET K 

View or change the K factor. The K factor is the number of 

pulses the flow sensor provides for every gallon of flow. 

(Note that the decimal is fixed at three places. If you only 

have two decimal places for your K-factor, enter a zero for 

the third digit. If unable to set K-factor, the unit is "locked" 

to prevent tampering. Please contact your distributor for 

assistance.)

R UNIT

View or change the flow rate units

R UNIT

SET K

T UNIT

SET D

SET P

RESET

EXIT

086238.235

PRESS     TO SET NUMBER

OF PULSES RECEIVED PER

GALLON OF FLOW

R UNIT

SET K

T UNIT

SET D

SET P

RESET

EXIT

086238.235

PRESS     TO SET NUMBER

OF PULSES RECEIVED PER

GALLON OF FLOW

R UNIT

SET K

T UNIT

SET D

SET P

RESET

EXIT

FLOW RATE = GPD

PRESS    TO SET UNITS

FOR DISPLAY 

K-Factor

At a minimum, every FT430/440/450 flow computer must 

be programmed with the “K-factor”. (This is the number of 

pulses that the meter produces per gallon of flow.) If you 

wish to read in units other than gallons, see below.
The K-factor on any Seametrics flow sensor fitting or in-

line meter can be found on the model-serial label. The line 

reading K = xxxx gives the desired number. For depth-

adjustable  sensors  (110,  210,  150,  250  models),  use  the 

calculator on our website.  
(Refer to the appropriate instruction manuals for iMAG 

4700, AG3000 or WMP pulse settings.)
Note: The K-factor on all FT430/440/450 flow computers is  

expressed in 

pulses per gallon

 of flow regardless of rate or 

total units.

Find Your K-Factor Here

10031295

MF81T-P200

K: 53.6

Fixed Depth Meter

Содержание FT430

Страница 1: ...PROUDLY MADE IN THE USA C e rtified Compa n y ISO ISO 9001 FT430 440 450 FT430 440 450 Rate Total Indicator Rate Total Indicator Instructions Instructions Optional Protective Cover Closed...

Страница 2: ...3 Wire Mechanical Meter Page 8 Connections for FT430 139 or FT440 139 115Vac Option Page 9 FT440 3 wire Mechanical Dual Scaled Pulse Output Page 9 FT440 EX Magmeter Page 10 FT440 139 EX Magmeter Page...

Страница 3: ...the loop and sensors requiring more power than the loop can supply Pulse and 4 20mA analog outputs can be used to signal external devices e g certain metering pumps and water treatment controls Alter...

Страница 4: ...Mega Liters Day Million Gallons Day Fluid Oz Second Minute Hour Day Barrels Second Minute Hour Day Total Units Gallon Gallon x 1000 Liters Mega Liter Cubic Meter Acre Feet Cubic Feet Cubic Feet x 100...

Страница 5: ...h or Low YES High or Low YES High or Low PULSE OUTPUT 2 SCALED FT430 FT440 Note 2 FT450 TYPE Not Available Current sinking Not Available MAX VOLTAGE 36 Vdc MAX CURRENT 100 mA MAX FREQUENCY 6 5 Hz PULS...

Страница 6: ...sing to the depression on the top of the flow sensor 5 Using an ordinary screwdriver inserted in one side of the slot see drawing tighten the screw as much as possible 6 Strip the wire ends make the c...

Страница 7: ...installed on the cord grip and must be snugly tightened on the cable or on a plug that would take the place of the cable Plugs with flanges are to be installed from the outside of the compression nut...

Страница 8: ...ER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ RED WHITE BLACK Micropower Flow Sensor FT450 Pulse Pass thru Pulse Responsive Metering Pump Current Sinking Polarity Sensitive Lithium C 3Vdc Replaceab...

Страница 9: ...40 139 115Vac Option POWER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ RED WHITE BLACK _ 9 30 Vdc Loop Power Supply Flow Sensor FT440 Electronic Metering Pumps _ S _ _ _ 4 20mA Device _ GROUND Conne...

Страница 10: ...orward Output Power M ax6m A 30Vdc 12 24Vdc _ _ White Green Red Black POWER SENSOR ENGD _ _ S PULSE OUT 2 PULSE OUT 1 _ _ FT440 GREEN WHITE BLACK _ FT440 139 Dual Power Supply Lower Housing 4 20mA Dev...

Страница 11: ...TION DIAGRAMS FT4XX Sensus Tranceiver Connections FT4XX Eqipped with Sensus Board Side View Sensus Tranceiver Red Power Clock Black Ground Green Data Red Black Green NOTE A Sensus 2m 6 ft output cable...

Страница 12: ...ry gallon of flow Note that the decimal is fixed at three places If you only have two decimal places for your K factor enter a zero for the third digit If unable to set K factor the unit is locked to...

Страница 13: ...quals Set P R UNIT SET K T UNIT SET D SET P RESET EXIT TOTAL GALLONS PRESS TO SET UNITS FOR DISPLAY R UNIT SET K T UNIT SET D SET P RESET EXIT 000 PRESS TO CHOOSE NUMBER OF DECIMAL PLACES IN TOTAL DIS...

Страница 14: ...he P A tab changes the function of the scaled pulse outputs Default is scaled pulse Any scaled pulse output can be changed to alarm high or alarm low If alarm options are selected menu tabs for settin...

Страница 15: ...se output Wrong pulse output setting Use Set P to correct pulse output setting Polarity reversed on pulse output terminals Reverse leads Display reads normally but no or incorrect 4 20mA output FT440...

Страница 16: ...roducts or parts that are typically consumed during normal operation ix Use of parts or supplies other than those sold by Seametrics which cause damage to the products or cause abnormally frequent ser...

Отзывы: