- 6 - 

thermostat will automatically exit to the 

OFF

 mode. Note: All changes made in the 

configuration menu are automatically saved. 

 
CONFIGURATION MENU CHART 

See “Parameters” section for a detailed explanation of parameters and values. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PARAMETERS 

CC - Select Cooling Cycle Rate   

The FA setting produces shorter cooling cycles. The SL setting produces longer cooling 
cycles. FA cycles the system at a 0.75ºF differential (0.5°C), and SL cycles the system at a 
1.5ºF differential (1°C).   

HC - Select Heating Cycle Rate   

The FA setting produces shorter heating cycles. The SL setting produces longer heating 
cycles. FA cycles the system at a 0.75ºF differential (0.5°C), and SL cycles the system at a 
1.5ºF differential (1°C). 

CP - Select Compressor Lockout Delay 

To protect the compressor from short cycling, you can select the minimum length of time the 
compressor will turn off between cycles from 0 to 5 minutes in 1 minute increments. When a 
compressor lockout delay occurs, “COMP DELAY” will flash.   

Parameter 

Parameter 

Value 

Options 

Description 

Factory 

Defaults 

CC 

FA or SL 

Select cooling cycle rate: 

FA= fast    SL = slow

 

FA 

HC 

FA or SL 

Select heating cycle rate: 

FA= fast    SL = slow

 

FA 

CP 

0 to 5 

Select compressor lockout delay: 

0 = none,    1 to 5 = number of minutes delayed after last call 

AU 

1 to 10 

Select auxiliary heat offset: 

1to 10 = number of degrees below setpoint

 

bL 

1, 2, or 3 

Select LCD backlight duration: 

(1) = OFF    (2) = 30 seconds after any button push    (3) = always ON   

FL 

00, 1 to 12 

Select filter service time:   

00 = deactivated    1 to 12 = number of months (1 month = 30 days)

 

00 

FC 

F or C 

Select temperature scale:   

F = ° Fahrenheit    C = ° Celsius 

CL 

-4 to 4 

Select temperature calibration value: 

-4 to 4 = number of degrees above or below room temperature 

 

Содержание SN12I

Страница 1: ...Safety Information 1 Remove the Old Thermostat 3 Install the New Thermostat 4 Configuration 5 Configuration Menu Chart 6 Parameters 6 System Check 8 Basic Thermostat Operation 9 Troubleshooting 10 Wa...

Страница 2: ...n clock function IMPORTANT SAFETY INFORMATION Use a professional contractor to install this thermostat Read all of the information in this manual before installing this thermostat WARNING Electrical S...

Страница 3: ...vice Reminder Time Day Setting Low Battery Icon Configuration Compressor Lockout Delay SET TO AM MON SERVICE FILTER CONFIG COMP DELAY ON AUTO AUX EMH Figure 1 THERMOSTAT BUTTONS AND SWITCHES Figure 2...

Страница 4: ...OFF position 3 Remove the cover of the old thermostat This should expose the wires 4 Label the wires from the existing thermostat using the enclosed wire markers and record in the chart below before r...

Страница 5: ...ing screws and anchors provided mount the thermostat base loosely to the wall or junction box See Figure 3B 6 Place a level against the bottom of the base and adjust until level then tighten the screw...

Страница 6: ...the battery compartment Install two fresh AA alkaline batteries in the battery compartment CAUTION Installing batteries backwards can damage the thermostat Be sure to match positive and negative ends...

Страница 7: ...compressor from short cycling you can select the minimum length of time the compressor will turn off between cycles from 0 to 5 minutes in 1 minute increments When a compressor lockout delay occurs CO...

Страница 8: ...the number of days is also displayed in the upper left corner of the LCD A selection of 00 will deactivate this feature When SERVICE FILTER is displayed in EMH HEAT or COOL mode it can be cleared by...

Страница 9: ...ow setpoint and turn off at setpoint The auxiliary heat will activate when the room temperature is below the setpoint by the auxiliary heat offset value AU plus heating cycle rate value HC as establis...

Страница 10: ...e SL ow cooling cycle rate is selected the thermostat will call for cooling when the room temperature is 1 5 F 1 C above setpoint and turn off at setpoint 3 When the thermostat calls for cooling will...

Страница 11: ...e If no buttons are pressed within 15 seconds the thermostat will exit to normal operation 4 In filter review mode press and hold the and buttons at the same time to reset the amount of time until the...

Страница 12: ...itations or ex clusion may not a pply to you INTERNATIONAL REFRIGERATION PRODUCTS CO INC LIMITED WARRANTY POLICY INTERNATIONAL REFRIGERATION PRODUCTS CO INC Langhorne PA 19047 www irproducts biz INTE...

Отзывы: