8
2. SpecificationS
clearances & Hearth- axis i1000iB doUBle Sided
siDE
Front
toP
1300MM
non-CoMBustiBlE
stuD
100MM
non-CoMBustiBlE
100MM
air gaP
100MM
air gaP
100MM
air gaP
*all diagrams are not to scale
Floor ProtECtor
(Must BE a Fully
suPPortED BasE)
this appliance and flue were tested with the following minimum clearances.
the axis i1000iB double sided and Z/c box was tested in a combustible enclosure in a manner
conforming to aS/nZS 2918:2001, appendix B. the sides of the wall enclosure must be no closer than
100mm
from the sides of the appliance zero clearance box. The front and rear wall of the enclosure
must be made of a non-combustible material to a height of
500mm
above the appliance fascia and
must extend to
100mm
either side of the appliance fascia. the internal wall studs of the appliance must
also be made of a non-combustible material.
important: mantel sHelf:
mantel shelf and mantel upright clearance was not tested and should
be installed as per clause 3.4.1.3 (b) of AS/NZS 2918:2018.
a minimum
1605mm
deep X
1300mm
wide X
42mm
thick floor protector (Skamotec board or similar)
should be used under and in front of the appliance base when installing the appliance (refer to aS/nZS
2918:2018 3.3.2). The floor protector should extend
550mm
in front of each fuel loading door and be
placed centrally in the
1300mm
width.
The appliance is required to be installed on 40mm high spacers inside the zero clearance box between
the appliance and the base of the zero clearance box.
please note
:
a minimum 50mm air gap must be maintained around the outer triple skin flue skin in
the ceiling of the enclosure.
100MM
non-CoMBustiBlE
Min 100MM
it is the users duty to make themselves aware of and apply all national or more restrictive local
standards and instructions (AS/NZS 2918:2018).
iMPortant
Prior to unpacking and installation ensure the appliance has not been damaged during transit. Please
ensure you check the glass, the door(s), the damper operation and the door locking mechanism
Before any work is carried out, as per local and national regulations and laws, this appliance Must be
installed by a licensed professional as per as/nZs 2918:2018.
iMPortant Warning
any exception or altercations beyond this manual and as/nZs 2918:2018 is a health and safety hazard
which will result in a non-compliant installation and a void of warranties.
Electrical cables and components must not be placed in the vicinity of the appliance as it is a fire
hazard.
3. preliminary inStall GUide
siDE
505MM
550MM
MiniMuM
90MM
air gaP FroM
CoMBustaBlEs
500MM
non-CoMBustiBlE
stuD
non- CoMBustiBlE
550MM
42MM
100MM
air gaP
500MM
non- CoMBustiBlE
100MM
air gaP
Min 100MM