background image

6

IN

 AU

STRAL

IA

PR

OU

DLY BUILT

Continued Over.../

A message is not a valid message if:

• 

It contains more than 80 characters before an end of message character is received.

• 

It contains a character that is not <CR>,<LF>,<TAB>,<SPACE>,0,1,2,3,4,5,6,7,8,9,”,”.

• 

A numerical field exceeds 65535

• 

It contains more than 10 fields

If a packet is determined to be not a valid message it is ignored. If a message is determined to 
be invalid before the end of message is ignored then all characters received are ignored until an 
end of message character is received.
Messages from the IP Connect module comply with the requirements of the incoming 
messages but in addition are fixed width formatted. Each numerical field is made of 5 
characters (leading spaces and digits). A comma delimiter is included. 
An Example is shown below:
1, 3, 45<CR><LF> 

INSTRUCTIONS - 

MASTERFIT IP 

A, A+, B, B+, C, C+ Projection Screen

15. CONTROL COMMANDS

• 

These commands are used to control the operation of screens.

• 

The Switch groups and IR groups must be programmed according to section 5

• 

Unified address is MAF address plus 16 e.g. Module 1 is Unified address 17

OPERATE MODULE DIRECT

• 

Command followed by value 0 operates all modules connected via Connect Network 
including the Connect IP module  
(e.g.: 30 0 will operate all devices connected via the Connect network) 

• 

Example of direct command  
Connected to 192.168.0.32:3002 – command 30 1 using module ID would see the screen 
move to up position

OPERATE IR GROUP

IR GROUP COMMANDS

• 

IR group control can be used to control screens directly if connected via Connect Network 
including the Connect IP module

• 

Each module will require programming via register 75, as per point 11 in document

• 

Example of direct command Connected to 192.168.0.32:3001 – command 20 1 ,would see all 
screens programmed to operate on IR group 1 move to up position

• 

Command followed by value 0 operates all modules connected via Connect Network 
including the Connect IP module

COMMAND

VALUE

DESCRIPTION

30

Module ID

Operate Module UP

31

Module ID

Operate Module PARTIAL 1

32

Module ID

Operate Module PARTIAL 2

33

Module ID

Operate Module DOWN

36

Module ID

Operate Module STOP

COMMAND

IR GROUP

DESCRIPTION

20

IR Group 1 to 9, 0

Operate IR Group UP

21

IR Group 1 to 9, 0

Operate IR Group PARTIAL 1

22

IR Group 1 to 9, 0

Operate IR Group PARTIAL 2

23

IR Group 1 to 9, 0

Operate IR Group DOWN

26

IR Group 1 to 9, 0

Operate IR Group STOP

OPERATE SWITCH GROUP

SWITCH GROUP COMMANDS

• 

Switch group control can be used to control screens directly if connected via Connect 
Network including the Connect IP module

• 

Each module will require programming via register 74, as per point 11 in document

• 

Example of direct command  
Connected to 192.168.0.32:3001 – command 20 1 - would see all screens programmed to 
operate on Switch group 1 move to up position

• 

Command followed by value 0 operates all modules connected via Connect Network 
including the Connect IP module

COMMAND

IR GROUP

DESCRIPTION

10

SWITCH Group 1 to 9, 0

Operate IR Group UP

11

SWITCH Group 1 to 9, 0

Operate IR Group PARTIAL 1

12

SWITCH Group 1 to 9, 0

Operate IR Group PARTIAL 2

13

SWITCH Group 1 to 9, 0

Operate IR Group DOWN

Содержание MASTERFIT IP

Страница 1: ...ntact input Requires momentary contact only Contact is closed and opened between Up Common screen moves to up limit Contact is closed and opened between Down Common screen moves to bottom limit Stop command is sent when both Up Down contact closed together 2 Infra Red Receiver Packaged with 300mm and 1 2 M lead from motor board to IR receiver Packaged with standard 2 channel IR transmitter Screen ...

Страница 2: ...witch Clockwise always increases the amount of rotation travel of the motor Anti clockwise always reduces the amount of rotation travel of the motor So pick the switch responsible for the limit position up or down Clockwise turning of the switch will always let the motor travel further in that direction Anti clockwise turning of the switch will lessen the amount of travel in that direction Can I a...

Страница 3: ...ion in Connect network of up to 9 and Module ID same as MAF unless changed in programing is shown Simple control operation for test set up Status indication of screen use refresh to obtain latest status update 9 GROUP CONTROL Select the Control tab and use dropdown box to choose Group Control Control Screens that have been programmed with the same IR group or switch group contact Close input Parti...

Страница 4: ... IP operating parameters e AMX Discoverable enable f Screen Technics Beacon g Simple control page Continued Over INSTRUCTIONS MASTERFIT IP A A B B C C Projection Screen 11 REGISTER SETTINGS Access this menu by selecting System then Module Settings Select MAF address or Module ID and select load Change value and select update This menu will enable changes of features within the module 127 registers...

Страница 5: ...ister 74 to a value of 2 If you wish the module to operate on Group 1 2 only change register 74 to a value of 6 SWITCH GROUP BITMAP REGISTER Calculate the register number by using the table Transfer the value for each required group to the right column The total of the values in the right column then becomes the Register Value E g to set groups 1 2 4 then the Total value is 22 Group Value 1 2 2 4 ...

Страница 6: ...NDS IR group control can be used to control screens directly if connected via Connect Network including the Connect IP module Each module will require programming via register 75 as per point 11 in document Example of direct command Connected to 192 168 0 32 3001 command 20 1 would see all screens programmed to operate on IR group 1 move to up position Command followed by value 0 operates all modu...

Страница 7: ... 2 VALUE 3 150 Status Module ID Module Status Register 0x20 Response from module e g 150 1 1 6 value 6 indicates screen at top Note Status 1 is returned if valid data and no further records in the status buffer Status 2 is returned if valid data and there are still records in status buffer Status 3 is returned if valid data but the buffer is full eg may have lost data Status 6 is returned if there...

Страница 8: ...ction is exited when screen operation finished or another screen operate command is acted on Double short press for 2 seconds approximately per button press Screen Up command Screen travels to up limit LED single flashes while in this function Pressing button again stops screen Function is exited when screen travels to up position or another screen operate command is sent Triple short press for 2 ...

Отзывы: