Service Diagnosis
Service Diagnosis
•
What happens if?
•
Both the solenoid valves in the condensing unit
do not work
– Very, very unlikely, but
•
The discharge pressure during harvest will be about 150
PSIG
•
The low side pressure during harvest will be less than 90
PSIG
•
The ice will harvest slowly
•
The refrigerant flowing out of the receiver will make a
whistling noise