Line Set Installation
Line Set Installation
•
Route lines in two groups
– Liquid and Vapor
– Suction separately for ease of routing
•
3/4” tube requires careful handling
– Check for holding charge before installation
– Route control wire with line set
– Only shorten if necessary
•
Do before connections are made!
•
Purge with nitrogen while brazing
– Schraders at both ends for purging
•
Evacuate to 300 microns or less
•
Add holding charge if connecting later