background image

Final Placement

After the utilities and refrigeration connections
have been made, secure the unit to the dispenser
or bin top.

Secure ice making section to dispenser or bin
adapter.

Use strap/clips to secure unit. On some bins or
dispensers it may be necessary to drill small holes
and use field supplied sheet metal screws to
secure the ice making head to that bin, dispenser
or adapter.

If the ice maker & bin or dispenser is not yet in its
final position gently move it there.

Note: The refrigerant lines above the machine
must be able to move freely while the machine is
being moved into position.

Final Check List Before Initial Start Up

1. Confirm that the ice making section is installed

indoors in a controlled environment.

2. Confirm that all packing materials have been

removed from all products.

3. Confirm that the ice making section is level.

4. Confirm that all the refrigerant connections

have been made and checked for leaks.

5. Confirm that the proper power supply has been

turned on to the condensing unit.

6. Confirm that cold, potable water has been

supplied to the ice making section and checked
for leaks.

7. Confirm that the water supply is adequate.

8. Confirm that there is adequate water pressure

and that any water filters have been checked to
confirm that the cartridges do not need
changing.

9. Confirm that the proper size drain tubing has

been installed and properly routed.

10. Confirm that the ice making section has been

connected to the proper power supply.

11. Confirm that the interconnecting wire has been

routed and connected between the ice making
section and the compressor package.

12. Confirm that the bin thermostat has been

properly installed.

Eclipse

ä

1300, 1600

September 2003

Page 26

Содержание CME1386

Страница 1: ...section Page 18 Bin Thermostat Routing Page 19 Bin Thermostat Bracket Bulb Page 20 Water and Drain Page 21 Water and Drain Page 22 Ice Making Section Set Up Page 23 Coupling Connections Page 24 Condensing Unit Connections Page 25 Final Placement Page 26 Controller Operation Page 27 Initial Start Up 1300 and 1600 Page 28 Purge Adjustment Page 29 System Operation Page 30 Refrigeration Details Page 3...

Страница 2: ...mponents not specifically approved by Scotsman Scotsman reserves the right to make design changes and or improvements at any time Specifications and design are subject to change without notice Warranty Refer to the warranty coverage in effect when the equipment was sold Warranty statements are included with each product Systems Each sub system is a separate entity that carries its own model and se...

Страница 3: ...inimum Circuit Ampacity Max Fuse Size Cabinet Size Weight lb CME1386RLS 1A 115 60 1 3 15 30 w x 24 d x 28 h 144 CME1686RLS 1A 115 60 1 3 15 same 154 Model Voltage Contains Headmaster Minimum Circuit Ampacity Max Fuse Size Refrigerant Charge R 404A Cabinet Size Weight lb CP1316 32A 208 230 60 1 Yes 24 3 30 18 lb 29 w x 18 d x 34 h 180 CP1316 3A 208 230 60 3 Yes 15 3 20 18 lb same 180 Includes entir...

Страница 4: ... the model number serial number electrical data and system refrigerant charge A second plate located behind the front panel in front of the compressor also lists the model number serial number and refrigerant charge Condenser The dataplate lists the condenser s electrical information plus the model and serial numbers On the ERC1086 it is located on the side opposite the refrigeration connections E...

Страница 5: ...e 5 17 08 2 53 4 85 17 31 TOP VEIW ICE DROP AREA TOP ACCESS REFRIGERANT LINE SETS UTILITY CHASE 30 00 3 02 1 90 15 76 5 19 REAR VEIW WATER INLET 3 8 FLARE DRAIN 3 4 PVC FEMALE REFRIGERANT LINE SETS CONNECTIONS 24 00 3 18 Thermostat Routing Hole 13 from front 4 63 from side ...

Страница 6: ...CTRICAL INLET 3 4 SUCTION LINE INTERFACE HARNESS ACCESS HOLE 3 8 CONDENSER LIQUID LINE OUT 1 2 CONDENSER DISCHARGE LINE IN CONDENSER FAN WIRE ROUTING ERC680 or ERC1086 This Side Attaches to CP1316 27 90 28 53 35 72 2 75 Liquid Line Discharge Line 29 50 38 47 33 19 6 68 22 51 29 19 9 16 Mounting Hole 9 16 Mounting Hole 23 5 1 5 1 5 3 8 LIQUID LINE 15 1 5 1 5 ...

Страница 7: ...iple line set liquid vapor and suction Bin or dispenser adapter Special Considerations The ice making section s footprint is 30 wide by 24 deep The refrigeration connections can be made out the top panel or out the back The electrical power cord and the water inlet line can also be routed through either of those areas The drain may be routed out the back or to the left side The bin thermostat when...

Страница 8: ...e making section up to a limit of 15 feet Distance from unit Limited to the length of the available pre charged tubing Elevation CP unit limited to 35 feet above the ice making section Compressor package Electrical power must be supplied to the compressor package The remote condenser fan motor takes its power from the compressor package Ice making section location and attachment The 115 60 Hz ice ...

Страница 9: ... on either a single circuit condenser or onto a coil in a separate rack condenser Separate coils must be Scotsman approved The correct size and capacity New or not have been part of a system that used mineral oil Eclipseä 1300 1600 September 2003 Page 9 System on Ice Storage Bin System on Ice Dispenser ...

Страница 10: ...a non Scotsman condenser In that case the CP unit is NOT bolted to the condenser and a RTE10 line set is used to connect the refrigeration system to the condenser s coil Eclipseä 1300 1600 September 2003 Page 10 IMS on Bin CP Unit Connected to Approved Central Condenser Coil ...

Страница 11: ...e must also be reserved for service on the compressor package Roof Piercing The roof or wall must have a passage large enough for the three pre charged pre bent tubes and the control wire to pass through The minimum recommended size is 4 ID In most areas the power supply may also pass through the same passage If there isn t a passage one must be created In most cases this must be done by a license...

Страница 12: ...k Ice Making Section Elevation over Condensing Unit 15 feet Line Routing Allowed One rise after a drop Allowed One drop after a rise Not Allowed More than one rise after a drop Not Allowed More than one drop after a rise Eclipseä 1300 1600 September 2003 Page 12 22 87 17 15 40 35 Condensing Unit Distance Schematic Max Rise 35 Feet Max Drop 15 Feet Max Length Limit of Line Set Condensing Unit Locat...

Страница 13: ...o install it Identify the ice machine end of the tubing Each tube has one end formed to route through the hole in the unit s top Tape the ends of the vapor and liquid line tubes together along with the interconnecting wire Extend the end of the interconnecting wire about 2 feet beyond the end of the precharged tubes and then tape it back onto the tubes Route the three tubes and the wire from the r...

Страница 14: ...ens to allow pump to drain the reservoir Water Inlet Valve 2 77 GPM solenoid valve that opens to fill the reservoir Low Side Access Valve allows connection for diagnosis of ice machine section refrigeration operation Not for recovery Liquid Vapor and Suction Connections where the pre charged tubing kits connect to Eclipseä 1300 1600 September 2003 Page 14 Water Pump Water Level Sensor Drain Valve ...

Страница 15: ...g harvest Receiver stores liquid refrigerant for freeze and provides vapor for harvest Suction Access Valve provides a place to attach a refrigeration manifold for diagnostics and recovery Eclipseä 1300 1600 September 2003 Page 15 CP Unit Refrigeration Connection ID Power Routing Hole Vapor Line Connection 24 volt comm line Routing Hole Liquid Line Connection Suction Line Connection Liquid from Co...

Страница 16: ...e CP unit to ERC 11 Attach leg brace between ERC unit and CP unit 12 Route wires from condenser through hole in back of CP unit to the CP unit control box 13 Pull ERC female refrigerant connections forward to engage male connections on CP unit 14 Rotate swivel nuts to tighten refrigerant connections Use a back up wrench to hold female connection to prevent tearing of the diaphragms 15 Connect wire...

Страница 17: ...e of CP unit and plug into the connection on the bottom of the control box Route power conduit liquid tight and wires to the hole in the side of the CP unit Secure with the proper type of connector Note The power supply wires must be the correct size and type per the National Electric Code Locate the nameplate on the CP unit for the Voltage Phase Minimum Circuit Ampacity and Maximum Fuse Size Eith...

Страница 18: ...ispenser See sales information for the correct kit Place adapter kit onto bin or dispenser top If adapter does NOT have gasket tape install tape such as Scotsman part number 19 0503 04 Attachment If the unit is a direct fit place it on the bin If the unit is in a position that it need not be moved to complete the installation secure it to the bin with the hardware provided with the head unit On so...

Страница 19: ...refully position the thermostat bulb on the bracket see the diagram on the next page 5 Fasten the bracket to the bottom of the ice machine with the two 3 pronged knob head screws supplied with the unit 6 Pull back into the ice machine any excess capillary tubing 7 Return the baffle to the bin and continue with the installation Note If the machine is located at an altitude higher than 2 000 ft adju...

Страница 20: ...stat Bracket Bulb Eclipseä 1300 1600 September 2003 Page 20 Attach Thermostat Bulb to Bracket Mount Bracket to Bottom of ice Head Bracket Thermostat Capillary Tube Insert Tip into Hole Snap Tube Through Slot Bulb ...

Страница 21: ...nser and tight against the wall the drain must be routed through the area in the lower back of the left side panel In some tight situations it will be necessary to assemble the ice making section to the dispenser or bin and install the water and drain connections before placing the system in its installed position A loop of water supply tubing will allow movement of the system In other tight situa...

Страница 22: ...low preventer is required Drain Connect rigid drain tubing to the reservoir drain fitting Route the drain either out the back or to the left side Add a 18 vertical vent to the drain tube Route the drain tubing to the building drain Do not Tee into any other drain including the bin or dispenser drain Follow all local codes Eclipseä 1300 1600 September 2003 Page 22 Back View Drain Tubing Installed f...

Страница 23: ...the middle fitting Connect the liquid line to the bottom fitting See Coupling Connections on the next page for detailed instructions After couplings are connected add cork tape type insulation to exposed fittings to reduce condensation potential Eclipseä 1300 1600 September 2003 Page 23 Refrigerant Lines Shown Routed Out The Top Add insulation Suction Vapor Liquid Refrigerant Lines Shown Routed Ou...

Страница 24: ...ned or the diaphragms will be torn by the piercing knives and become loose in the refrigeration system causing severe operational problems Note As the coupling is tightened the diaphragms in the quick connect couplings will begin to be pierced As that happens there will be increased resistance to tightening the swivel nut 4c Continue tightening the swivel nut until it bottoms out or a very definit...

Страница 25: ... line to the matching fittings on the CP unit See Coupling Connections on the prior page for detailed instructions Eclipseä 1300 1600 September 2003 Page 25 Assembled Condensing Unit Control Wire Power Supply Inlet Field Supplied Service Disconnect Liquid Line Suction Line Vapor Line ...

Страница 26: ...materials have been removed from all products 3 Confirm that the ice making section is level 4 Confirm that all the refrigerant connections have been made and checked for leaks 5 Confirm that the proper power supply has been turned on to the condensing unit 6 Confirm that cold potable water has been supplied to the ice making section and checked for leaks 7 Confirm that the water supply is adequat...

Страница 27: ...part of the cleaning process Push and release again to start the second part of the cleaning process Off Push and Release to shut the machine off at the end of the next harvest cycle Push and Hold for three seconds to stop the machine Push and Hold again to go into the Purge Adjustment or Error Recall mode Cycle Definitions Freeze The refrigeration system is operating to remove heat from the evapo...

Страница 28: ...a few minutes ice will begin to form on the evaporators When enough ice has formed to nearly empty the water reservoir the controller will refill the reservoir The next time the water level drops that far the ice is ready for release and the Controller will initiate a Harvest cycle The Freeze light goes out and the Harvest light switches on The vapor inlet valve in the ice making section opens In ...

Страница 29: ... this light is ON Off For excellent water conditions Adjust by pushing and releasing the Freeze button Pushing and releasing the Freeze button increases the purge one level up to the maximum then it goes to the minimum 4 The machine will automatically restart after 60 seconds of no switch inputs or restart the machine by pushing in and holding the Off button for more than 3 seconds then releasing ...

Страница 30: ...orators until it begins to freeze to the evaporators As ice builds up the water level in the reservoir falls until it reaches a point where the water level sensor indicates to the controller that the water level is low At that point about half way through the freeze cycle the controller opens the water valve to refill the reservoir The second time the water level drops in the freeze cycle indicate...

Страница 31: ...ondensing unit where it enters the accumulator In the accumulator most of any liquid carried with the suction gas is separated and only vapor flows out of the accumulator through the CPR valve and to the compressor where the cycle continues During harvest discharge gas flows through the open condenser by pass valve into the vapor line Power is also applied to the coil of the liquid inlet valve clo...

Страница 32: ...he temperature it expects to find at that point in the cycle If normal nothing happens If high the controller checks the discharge temperature If that is normal nothing happens If that is low the controller starts a diagnostic process that could lead to the unit shutting off as the refrigeration system may not be operable 6 Assuming that the system is working normally the controller will shut the ...

Страница 33: ...o Ice Released If no ice is sensed harvest continues until it reaches its pre set maximum when the controller switches the unit back into freeze Shut Down Maximum Harvest Time If a maximum harvest time is reached again during the next harvest cycle the controller will shut the system down and blink the refrigeration diagnostic light It will automatically attempt a restart in 50 minutes If the maxi...

Страница 34: ... cycle starts Water Interruptions The water level sensor checks for water fill whenever the water inlet valve is activated If the water level sensor does not record a full reservoir within the pre set time the controller shuts the unit off blinks the water diagnostic light two times and repeats After 20 minutes the inlet water valve is powered again and if the water level sensor is satisfied the u...

Страница 35: ...e ice machine cleaner has circulated for 10 minutes push and release the Clean button This starts the rinsing process The Clean indicator light will be ON Note The rinse process flushes any residual cleaner out of the ice machine s water system 10 Continue the rinsing process for 20 minutes then push the off button to switch the machine off 11 Go to the next step to sanitize the machine or go to s...

Страница 36: ...ghten any damaged fins with a fin comb If the coils have become coated with grease a coil cleaner will have to be used to wash the coils Disconnect power to the condensing unit and remove the condenser top Inspect the fan blade to be sure it is not cracked and is clean Return the condenser top to its original position and reconnect the power supply Eclipseä 1300 1600 September 2003 Page 36 Moving ...

Страница 37: ...inse process After 20 minutes push and release the Off button 14 Push and release the Freeze button 15 Return all covers and panels to their original positions Inlet Water Valve Screen The inlet water valve has a screen on its inlet side to keep debris from flowing into the valve In some cases this screen may become clogged or restricted by debris build up Check for the proper water flow Flow rate...

Страница 38: ...ray flips out of its socket 11 Wipe the lens clean with a soft cloth dipped in an ice machine cleaner solution 3 parts water to 1 part ice machine cleaner Do NOT use any abrasives on the lenses 12 Return the tray to its normal position Be sure it snaps into place The gray wire must be secured under the black plastic clip 13 Return each ice sensor to its normal position Be sure no wires are pinched...

Страница 39: ...age measures correctly proceed to the next step 5 Reconnect the harness Be SURE it is on properly and has a good connection To confirm unplug the harness from the water sensor and redo step 4 at the end of the harness Then plug the harness back onto the sensor Harness Connected Voltage DC 6 At the controller measure the voltage between the top and bottom pins on connection 2 This should be between...

Страница 40: ...ensor operation including harness between sensor and controller Ice making section has exceeded maximum freeze time and controller has shut down the system Condenser coils may need cleaning Check condenser fan blade and motor Check for excessive air intake temperatures at condenser coil Check compressor contactor Check compressor and starting components Check water pump Check purge valve for leak ...

Страница 41: ...ve during harvest No ice sensed during harvest Ice sensing system failure Check sensing system by pouring about 10 ice cubes through the ice outlet port The bin full light should blink indicating that it has sensed the ice If not check the sensors Check the ice sensors Place an object between the ice sensors after 5 seconds the Bin Full light will be glowing steadily if not check operation of sens...

Страница 42: ... of drinks dispensed cold plate melting ice Suggest pre cooler for water supply to cold plate Vapor inlet valve leaks through slightly during the freeze cycle Check valve body for similar temperatures on inlet and outlet the outlet should be colder and frost develops on the tubes to the evaporators Splash shield missing out of position and water is cascading out of the reservoir Install or re secu...

Страница 43: ...ller Diagnostic Codes If a Diagnostic Light Water Light Refrigeration Light Blinks once and repeats Water pump will not start Very long ice harvest Blinks twice and repeats Lack of water fill No harvest of ice Blinks three times and repeats not used High discharge temperature Is ON all the time Water valve leaking thru rapidly Maximum freeze time Both ON all the time Check for thermistor set unplu...

Страница 44: ...Compressor Amps Single Phase 15 Three Phase 8 Batch Weight 16 lb Discharge Pressure Cut Out Switch Cuts Out at 450 PSIG Resets at 350 PSIG Compressor CS20K6E Expansion Valves 1 Eclipseä 1300 1600 September 2003 Page 44 70 70 50 90 90 70 120 110 100 Freeze 12 to 13 minutes 16 to 17 minutes 26 to 28 minutes Harvest 3 minutes 2 minutes 1 minute 70 70 50 90 90 70 120 110 100 Suction at Ice Making Sect...

Страница 45: ...Amps Single Phase 15 Three Phase 8 Batch Weight 19 20 lb Discharge Pressure Cut Out Switch Cuts Out at 450 PSIG Resets at 350 PSIG Compressor CS20K6E Expansion Valves 1 Eclipseä 1300 1600 September 2003 Page 45 70 70 50 90 90 70 120 110 100 Freeze 15 to 16 minutes 17 to 18 minutes 28 to 29 minutes Harvest 2 minutes 1 minutes 1 minutes 70 70 50 90 90 70 120 110 100 Suction at Ice Making Section end...

Страница 46: ...he machine shuts off recover the refrigerant 3 Remove compressor package covers 4 Attach recovery system to low side compressor process port valve 5 If the recovery system can recover liquid attach recovery system to high side receiver liquid line out valve Operate recovery system to remove refrigerant from the system No other points of attachment or solenoid activation are required Eclipseä 1300 ...

Отзывы: