Pag. 19-EN
19
8.4
MPXPRO and ULTRACELLA/EVO CAREL configuration.
When unit is connected to evaporator controller via RS485, regulation type switch
automatically from fixed to floating set-point.
Select “Evaporator” and press “Enter”
Select “Configuration” and press “Enter”
Type of controllers connected to the CDU
Number of evap. and capacity of each unit
It is important to set the right serial address for each evaporator installed, with following
sequence:
11 – 12 – 13 – (14 – 15).
Different sequences and address not allowed!
Set of effective cooling capacity in order to maximize the result of energy savings with floating
suction regulation and in case of defrost
Basic information for each evaporator.
“Description”: name of refrigerated units
Start/Stop (On/Off) of evaporating management
and light, if present
Setting real clock for history alarm list