EN
OEM Manual – CUBO
2
AQUA
Pag. 14-EN
UMT/WG T MT Rev3.0 – 08/10/2021
14
Pipe length (m)
Liquid
line
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
K65 -
120bar
3/8’’(gr)
230
270
320
360
410
460
500
550
590
640
680
730
770
820
860
910
K65 –
120bar
1/2’
(gr)
410
490
570
650
730
810
900
980 1060 1140 1220 1300 1380 1470 1550 1630
K65 –
80 bar
1/2’
(gr)
450
530
620
710
800
890
980 1070 1160 1250 1340 1420 1510 1600 1690 1780
Examples of refrigerant charge calculation
Example 1
Receiver
Standing charge
2.4 kg
PHE Gas cooler
Standing charge
0.21 kg
Evaporator Volume 2 dm
3
Calculated from first graph
0.9 kg
Pipe length 8m x K65 3/8”
Calculated from second graph
0.4 kg
Pump
down
(from
evaporator)
Receiver / Evap
≤
7.2 kg
3.3 kg
Total System Charge
Receiver / Gas Cooler / Liquid line/ Evap
≤
7.2kg
3.9 kg
Is charge >4kg (min charge)?
Charge < 4 kg
3.9 kg
Total refrigerant to charge is 4kg.
Example 2
Receiver
Standing charge
2.4 kg
PHE Gas cooler
Standing charge
0.21 kg
Evaporator Volume 12 dm
3
Calculated from first graph
5.2 kg
Pipe length 8m x K65 3/8”
Calculated from second graph
0.4 kg
Pump
down
(from
evaporator)
Receiver / Evap
≤
7.2 kg
7.6 kg
Total System Charge
Receiver / Gas Cooler / Liquid line/ Evap
≤
7.2kg
8.21 kg
Is charge >4kg (min charge)?
Charge >4 kg
8.2 kg
Configuration not permitted. In pump-down condition the refrigerant inside the receiver
exceed the max quantity (7,2kg)
Don’t
overfeed the unit with excessive charge to avoid compressor damaged.