25
12.6 Set Economy mode - cooling:
•
Press again to set Economy Mode for cooling - the LCD will show
"EC ##" and
"COOL"
(Where "##" stands for set-point temperature for cool in economy mode –
two digits) (From 36
°
F-99
°
F or 4
°
C-38
°
C - default=77°F or 25°C).
12.7 Set Economy mode - Heating:
•
Press again and set Economy Mode for heating - the LCD will show
"EC ##" and
"HEAT"
(Where "##" stands for set-point temperature for heat in economy mode –
two digits) (From 35
°
F-98
°
F or 3
°
C-37
°
C - default=60°F or 15°C).
13. Connection of External Sensor
Important! The external sensor must be SCI type.
N.TC. Sensor: Temperature ~ Resistance Characteristics
Temp
°
C
7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2
Temp
°
F
45 50 55 60 65 70 75 80 85 90
Res. k
115.8 100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6
•
Disconnect power to the thermostat 24Vac.
•
Move Jumper 1 (on front plate) to position A. see # 4.1
•
Connect the temperature sensor to T1,0 terminals.
•
Reconnect power 24Vac.