701 Motor Protection Relay
Date Code 20010719
Settings Calculation
Voltage-Based Protection (Relay Models 0701001X & 0701011X)
4.38
Phase-to-Neutral Under- & Overvoltage Elements
Table 4.28
Under- and Overvoltage Settings, Phase-to-Neutral Potentials
When you connect the SEL-701 Relay voltage inputs to phase-to-neutral
Figure 2.6 on page 2.7 in Section 2: Installation
or
page 2.9 in Section 2: Installation
, the relay provides two levels of phase-to-neutral
overvoltage and undervoltage elements, plus a residual overvoltage element. The
residual overvoltage element operates using the phasor sum of the three phase voltages
and is hidden and disabled if only a single phase-to-neutral VT is connected to the
relay. You may use these elements for tripping, alarming, or supervision of other
conditions through the relay programmable logic described in
Control Equations & Relay Logic
. To disable any of these elements, set the pickup
settings equal to OFF. The default 27P1P setting provides undervoltage supervision for
the underpower, reactive power, and power factor tripping elements.
Reactive Power (VAR) Elements
Table 4.29
Reactive Power Element Settings
Table 4.28
Under- and Overvoltage
Settings, Phase-to-Neutral Potentials
Setting Prompt
Setting Range
Setting Name =
Factory Default
Level 1 Phase U/V Pickup
OFF, 1–300 V
27P1P = 40
Level 2 Phase U/V Pickup
OFF, 1–300 V
27P2P = OFF
Level 1 Phase O/V Pickup
OFF, 1–300 V
59P1P = 73
Level 2 Phase O/V Pickup
OFF, 1–300 V
59P2P = OFF
Residual O/V Pickup
OFF, 1–300 V
59GP = OFF
Table 4.29
Reactive Power Element Settings
Setting Prompt
Setting Range
Setting Name =
Factory Default
Negative VAR Alarm Pickup
OFF, 30–2000 VAR
a
NVARAP = OFF
Positive VAR Alarm Pickup 30–2000 VAR
a
PVARAP = 2000
VAR Alarm Time Delay
0.00–400.00 s
VARAD = 0.00
Negative VAR Trip Pickup
OFF, 30–2000 VAR
a
NVARTP = OFF
Positive VAR Trip Pickup 30–2000 VAR
a
PVARTP = 2000
VAR Trip Time Delay
0.00–400.00 s
VARTD = 0.00
VAR Element Arming Delay
0–15000 s
VARDLY = 10
a
Setting range shown for ITAP = 5 A. Range is 6–400 VAR when ITAP = 1 A.
Содержание SEL-701
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 36: ...This page intentionally left blank ...
Страница 64: ...This page intentionally left blank ...
Страница 144: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 232: ...This page intentionally left blank ...
Страница 246: ...This page intentionally left blank ...
Страница 346: ...This page intentionally left blank ...
Страница 390: ...This page intentionally left blank ...
Страница 408: ...This page intentionally left blank ...
Страница 410: ......
Страница 412: ......
Страница 414: ......
Страница 416: ......
Страница 418: ......
Страница 420: ......
Страница 422: ......
Страница 424: ......
Страница 426: ......
Страница 428: ......
Страница 430: ......
Страница 432: ......
Страница 434: ......
Страница 436: ......
Страница 438: ......
Страница 440: ......
Страница 442: ......
Страница 452: ...This page intentionally left blank ...
Страница 466: ...This page intentionally left blank ...