Parameter [Expert]
Zone1 - Zone4:
RTS offset: 0°C
Preheating time: Off
Heating gradient: 0.10min/K²
KP: 20
Tn: 120 sec
Tv: 0 sec
Luminous heater:
Minimum running time: 120s [2min]
Minimum pause time: 60s [1min]
Minimum full load: 60s [1min]
Fan lag time: 180s [3min]
Tube heater:
Minimum running time: 600s [10min]
Minimum pause time: 60s [1min]
Minimum full load time: 60sec [1 min]
Fan lag time: 900sec [15min]
Warm air heater:
Minimum runtime: 300sec [5min]
Minimum pause time: 60sec [1min]
Minimum full load time: 60sec [1min]
Fan lag time: 0sec [0min]
Single-stage
Switch-off threshold: 5%
Switch-on threshold: 20%
Two-stage
Switch-off threshold: 5%
Switch-on threshold: 20%
Full load threshold Off:50%
Full load threshold On: 60%
Modulating
Switch-off threshold: 5%
Switch-on threshold: 20%
Modulation start value: 90%
12.4.
QR Code
The QR code on the type plate and in the info screen of the connected control opens the
SchwankControl product information within the Schwank website.
As soon as the SchwankControl is connected to a computer or the local network with a LAN cable
[connection only available on control unit] and an IP is displayed in the info screen, the QR code that
starts the webapp within a browser window during scanning changes, see section 13.5
Содержание 40660000
Страница 39: ...Revision 3 0 Page 38 of 70...
Страница 40: ...Revision 3 0 Page 39 of 70...
Страница 41: ...Revision 3 0 Page 40 of 70...
Страница 54: ...Revision 3 0 Page 53 of 70 10 10 Characteristic sensor curves 10 10 1 Temperature sensor...
Страница 55: ...Revision 3 0 Page 54 of 70 10 10 2 Humidity sensor...
Страница 58: ...Revision 3 0 Page 57 of 70 11 4 2 Wiring for converter MODBUS RTU KNX Comes with the adapter in printed form...
Страница 67: ...Revision 3 0 Page 66 of 70 13 EU Declaration of Conformity...