2.2
Checklist
☐
Do you have the right mounting set for your mounting position?
The standard mounting set supplied with this fan for I-beam, allows the fan to be hung on
steel beams. Do not mount the fan on a purlin or a framework.
If you are unsure, please contact customer service.
☐
Has a structural engineer checked and approved the assembly position?
The assembly structure must withstand the forces generated by the fan.
☐
The fan is NOT used in parallel with heaters with indirect exhaust gas systems (unflued).
Otherwise, parallel operation must be prevented by interlocking it.
☐
The fan is at a minimum distance from the ceiling in accordance with the specified safety
distances.
☐
The fan´s wings are installed at least 3.5 m above the floor.
☐
The fan is installed with a minimum distance of 2 times the fan diameter from obstacles and
building structure, measured from the fan centre.
☐
The distance between several fans is at least 2.5 times the fan diameter, measured from
the fan centre.
☐
The fan is installed that it is not exposed to strong winds and maintains a safety distance of
at least 1 times the fan diameter from other heating, ventilation, air conditioning systems or
from gates.
☐
The supply voltage is selected correctly.
☐
The fan can be secured with the supplied safety ropes
There are mounting points available for the safety ropes.
If your fan application does not meet these requirements, proper operation is not
guaranteed. Please contact your customer services.