Assembly and installation
01.03|MV 15 - 30|en
15
Start-up
WARNING
Risk of injury due to objects falling or being ejected from the
machine/automated system!
• Check whether all micro valves are tight prior to the start-up
or restart.
Micro valves with the LP / P pressure range need a minimum
supply pressure in order to work. These micro valves are only able
to switch with this pressure support.
1 Supply pressure in the pressure range of the micro valve, see
catalog data sheet.
2 Apply the operating voltage.
The LED on a screw cap lights up.
3 Check whether the micro valve opens.
The supply pressure is put through to the valve outlet.
4 Switch off the operating voltage.
The LED on a screw cap goes out.
5 Check whether the micro valve closes.
The valve outlet is separated from the supply pressure and,
in the case of 3/2 control valves, is ventilated via the vent
connection in the valve cover.
6.6