background image

02/2022

 

• 

L-01431-4-08

                                                                

15 

!

 Alert the emergency light unit to the presence of a new battery: 

Open and close the lid of the battery box twice within a 60-second period. Opening and closing the 
case must occur within 10 seconds of each other.  
If this procedure is done correctly, immediately after the battery box is closed for the second time, 
the signal LED will display an acknowledgement light. The five-second long red-green 
acknowledgement light confirms that a operational life test will be conducted 12 hours later. 

 

 Close the lid of the battery box with the screw plug. 

 

Should a battery capacity fault be present when the acknowledgement light is displayed, more 
operational life tests will then be carried out at 52 week intervals. If no fault was detected in the batt ery 
capacity, the interval until the next regular operational life test is unaffected. 

 

6.5   Replacing emergency light unit and LED-reflector 

 

Replacement of the emergency light unit and LED-reflector with mounted LED-modules has been 
described in the separate instructions which can be found attached to the spare parts to be 
supplied. 

 

6.6   Environmental advice 

 

This device has got an accumulator which among other things contains 
cadmium which is ecologically dangerous. There is a particular 
designation for this purpose.  
The people operating this device are obliged by law to return 
accumulators which have become waste and which contain any pollutant 
materials to organizations which are in the hands of the vendors or 
waste disposal holders being under public law. 

 

6.7   Placing the fitting out of operation 

 

To place the light fitting out of operation the battery must be separated from the emergency  light unit.  
In order to avoid unnecessarily removing the emergency battery, disconnection should take place 
immediately after the interruption of the power supply.

 

 

During storage there will also be a gradual discharge of the battery. If the voltage drops below a 
certain level the battery will no longer be detected by the emergency light unit. Thus a battery contact 
failure will be indicated although the connection to the battery still exists. In this case, the emergency 
battery is to be removed as described in Section 6.3 and to be charged separately from the light fitting. 
A charging voltage of 6 V and a charging current of 80 mA must not be exceeded. Under these 
conditions is a discharged emergency battery sufficiently charged within just 5 minutes for it to be 
reinserted into the light fitting, where it can continue to charge.  

 

  To avoid any damages the battery should not be stored for more than 6 months 

without being re-charged periodically! 

 

 

 
 
 

 
 
 
 
 
 
 
 
 

Содержание e856 Series

Страница 1: ...and standards is mandatory for installation maintenance and repair of explosion proof equipment especially the determinations of IEC EN 60079 14 and IEC EN 60079 17 for maintenance of explosion proof appliances the generally accepted rules of the technical side the national rules for prevention of accidents and for safety standards the safety instructions of these operating instructions the charac...

Страница 2: ... or if the light fitting will be subject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequently the certification of this light fitting will be null and void So it is not allowed to drill through the housing for installation purposes Caution Risk of electrost...

Страница 3: ... either Due to harmful gases and other corrosive substances e g ammoniac sulphur or chlorine compounds it may come to damages of the LEDs Depending on the substance the concentration the temperature and the dwell time damages up to total black out are possible This may occur also to fittings with high degree of protection The suitability of the light fitting for the respective application can only...

Страница 4: ...erational life test to be carried out the emergency battery must be fully charged and connected For special versions with the option to deactivate the emergency light function the remote cutoff switch must also be closed Automatic operational life tests The first operational life test carried out automatically by the emergency light unit takes place at random within a period of 5 to 28 days after ...

Страница 5: ...yed more operational life tests will then be carried out at 52 week intervals If no fault was detected in the battery capacity the interval until the next regular operational life test is unaffected During the functionality and operational life tests the light fitting will switch on even if it was previously switched off 2 3 Ascertainable faults and reset of the display LED failure If a fault in t...

Страница 6: ...switch Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch Through a remote cutoff switch isolated switching contact it is possible to remove the light fitting from operation e g during maintenance With a remote cutoff switch it is possible to connect up to 30 light fittings cable cross section 1 5 mm cable length max 500 m The remote cutoff switch mu...

Страница 7: ...s C Power consumption The power consumption of the LED is dependent on production fluctuations as well as on the service temperature This is why just reference values can be given as follows e856 L05 6 W e856 L10 11 W e856 L20 19 W Possible number of light fittings per circuit breaker Cable entry Cable glands with thread size M25 x 1 5 if supplied sealing range 8 17 mm for 10 17 mm remove the smal...

Страница 8: ...1 1 6 ca 50 e856 L10 3 2 5 ca 25 e856 L20 1 1 6 ca 25 e856 L20 3 2 5 ca 13 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard version special version see type plate Art Nr 90222 9023 Typ 8021 6 V 2 5 Ah NiCd 3 hours emergency light time standard version special version see type plate Art Nr 90222 9024 ...

Страница 9: ...locking screw supplied with the fitting into the borings of the housing by using the lock nuts Torques see Chapter 3 Technical Data After mounting the light fitting housing insert the connection cable through the explosion proof cable gland An inlaid dust protective disc if existing must be removed before Fasten the pressing screw of the explosion proof cable gland Torque see Chapter 3 Technical D...

Страница 10: ...cted to the emergency battery it will not enter emergency lighting mode The electrical connection between the emergency battery and emergency light unit should be established as follows Version without battery box Remove the protective cap from the connector of the battery cable Attach the connector of the battery cable to the socket in the battery box Check the catch mechanism of the plug connect...

Страница 11: ...of lighting fitting please check and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are securely fixed in the housing Torques see Chapter 3 Technical Data the pressing screw of every explosion proof cable gland is tightened with the required torque Torques see C...

Страница 12: ...groups in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings or groups of light fittings may be exposed to unacceptably high voltages and consequently the emergency light unit may be destroyed ...

Страница 13: ...ttention to the following in case of application of this light fitting in dusty atmospheres Dust deposits show heat insulating properties and thus reduce the service life of the light fitting It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface temperature of the light fitting does not exceed the maximum permiss...

Страница 14: ... emergency light unit to the presence of a new battery Open and close the light fitting twice within a 60 second period Opening and closing must occur within 10 seconds of each other During this time the emergency light unit must be supplied by the mains supply If this procedure is done correctly immediately after the light fitting is closed for the second time the signal LED will display an ackno...

Страница 15: ...is ecologically dangerous There is a particular designation for this purpose The people operating this device are obliged by law to return accumulators which have become waste and which contain any pollutant materials to organizations which are in the hands of the vendors or waste disposal holders being under public law 6 7 Placing the fitting out of operation To place the light fitting out of ope...

Страница 16: ...02 2022 L 01431 4 08 16 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted ...

Отзывы: