Mess- und Regeltechnik

 

©2014 Schmidt 

Mess- und Regeltechnik

  

Fon 0 67 32 - 91 91 20        Fax 0 67 32 - 96 24 42        [email protected] 

3.4    Types of installation 
3.4.1 Port with weld neck flanges 

 

The complete flange type AU-FL includes 
screws and sealing at delivery.  

 

The overall height of 60mm must not be 
exceeded as this represents the reference 
dimension for the calibration of the 
instrument. 

 

The drill-hole to be made must be free of 
burrs. The screw holes must be offset by 
90° to the pipe axis. To seal the flanges 
please use the attached flat gasket. 

 

Please keep the flow direction in 
consideration during the mounting 
procedure (arrow). 

 

All pipes must be free of contaminants. 

 

 

3.4.2 Threaded connection

 

 

 

The tube is directly connected to the unit. We recommend sealing all threads with PTFE 
sealing tape. Ensure that no excess of tape is left protruding into the pipe. 

3.4.3 Flange connection

 

 

 

With a flange connection the sealing takes place between the device and flange by means of 
a suitable flat gasket (to be provided by the customer). Flat gasket and screws are not part of 
the delivery.  

4.

Electrical connection 

4.1   Connecting  type DW-P

 

 

Removing the device cover allows the 
connection of a micro-switch via the 
three-pole terminal block.  

 

The max. switching  capacity is up to 
230V/5A AC. 

 

The device is to be  grounded to the 
housing using the designated screw.  

Operation Manual 
Flowmeter / Flow Control DW-U 

 

Flow monitor after the baffle plate principle for liquids 

Содержание DW-U

Страница 1: ... for liquids Easy switch point adjustment in small scale steps Compulsive motion transfer to a micro switch Hermetic separation from the medium by means of bellows High power handling capacity Insensitive to magnetic fields High resistance to dirt and high operational safety Available for all flow directions Very economical monitoring of large pipes Output signal 0 4 20 mA for type DW U AN Without...

Страница 2: ...Switches and Flow Meters are to be installed directly into a pipe system Make sure that the instruments are installed according to the information given on the type plate The flow direction correlates to the direction of the pipe Inaccuracy of the instrument will result from incorrect mounting 3 2 Flow direction Due to the applied measuring principle the devices are functional only if for the inst...

Страница 3: ...edure arrow All pipes must be free of contaminants 3 4 2 Threaded connection The tube is directly connected to the unit We recommend sealing all threads with PTFE sealing tape Ensure that no excess of tape is left protruding into the pipe 3 4 3 Flange connection With a flange connection the sealing takes place between the device and flange by means of a suitable flat gasket to be provided by the c...

Страница 4: ...ing The max switching capacity is 230V 5A AC 4 2 Connecting Type DW U and DW N Removing the device cover allows access to the four pole terminal block In addition to the micro switch a control lamp is installed This lamp is for optical control of the switch status of the micro switch The required lamp voltage is indicated on the label The max switching capacity is 230V 10A AC Please connect the de...

Страница 5: ...s indicated on the small scale attached on the backside The actual flow is indicated on the large round scale at the front of the unit 7 Maintenance The Paddle Flow Switch Flow Meter DW U are virtually maintenance free In case of mal function first of all check the pipe system for calcification or contaminations For cleaning do not use sharp edged tools and proceed with extreme caution Damaged ins...

Страница 6: ... d In Zone 21 Dust Ex Category 2D at dusts with minimum ignition energy MIE 3 mJ e Usually there is no zone within the measuring tube Here Zone 1 may be set as maximum The qualification regarding the surface temperature is T4 for all gases vapours mists with an ignition temperature 125 C the mentioned devices are no ignition source In the dust EX category the reference temperature is 110 C Other m...

Страница 7: ...ed implicitly Sticking parts e g due to corrosion are not allowed to be removed violently in an EX atmosphere Protection measures against lightning are to be ensured by the operator 8 6 Repair and maintenance Definition of terms according to IEC 60079 17 Service and repair A combination of all activities that are carried out in order to keep an object in a condition or to repair it that it meets t...

Страница 8: ...easures Observance of the operation manual of the delivered construction groups Realization of the manufacturer s conditions 8 7 Troubleshooting It is not allowed to make changes on devices operated in explosion endangered areas Only legitimate technical personnel trained specially for this are authorized to carry out repairs on the device 8 8 Waste disposal The disposal of packaging and used part...

Отзывы: