Analog output
The analog output of the
MD 10.010
is galvanically isolated from its own
energy supply and the sensor supply (pin 13:
Analog Out+
; pin 12:
Analog
Out
–
≙
AGND; see Figure 2).
When using the display version with DC supply, the mass of the analog
output (AGND) can be connected to that of the operating voltage (GND).
However, the galvanic isolation is lost and a possible mass offset in the
connecting cable can lead to a distortion of the output signal.
When using the display version with AC supply, the analog output must
not be in contact with the supply voltage under any circumstances.
The load resistance R
L
has to be connected to AGND:
Current mode:
R
L
≤ 400
Voltage mode:
R
L
≥
1 k
In the configuration menu, beginning of signalization range without (0 mA
or 0 V) or with offset (signal transmitting zero point: 4 mA) can be selected.
5 Signalizations
Display
Display
State
Initialization of measured value display
Duration approx. 5 s (after switch-on of supply voltage)
Key lock activated
Error message of sensor
Flashing
Measurement range that can be displayed is exceeded or not reached
Table 2
Analog output
If the connected sensor indicates an error, the latter is also transmitted to
the analog output:
Output area without offset (0 ... 20 mA / 0 ... 10 V):
In current mode, the interface outputs 0 mA.
In voltage mode, the output switches to 0 V.
Output area with offset (4 ... 20 mA):
The interface outputs 2 mA.