![schmersal PSCBR-C-10 Series Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/schmersal/pscbr-c-10-series/pscbr-c-10-series_installation-manual_1213106062.webp)
Installation manual
Page 62 of204
DO0_P
X43
X42
DO0_M
DO1_P
DO1_M
NC
NC
DO.1
DO.2
X65
DI13
DI14
P1
P2
L +
L -
Fig.:
Single-channel switching output DO0_P with dual-channel external circuit as combination
of electro-mechanical element and hydraulic/pneumatic valve and monitoring at two inputs
Safety note:
Only conditionally recommended for safety applications! In this context see also the notes
in EN 13849-1 concerning the application and the required fault exclusions.
For PL c and higher a message/warning feature is required, which informs the operator
immediately about a dangerous situation
For higher requirements you must make sure that at least 1 switching operation must take
place every 24 hours, in order to test the switching ability of the external power contactor.