Functions of the Vacuum Switch
EN-US · 30.30.01.01602 · 01 · 10/18
39 / 58
The Reset to factory settings function does not affect:
•
Counter statuses
•
The zero-point adjustment of the sensor
•
The maximum and minimum values of the measurements
8.11.2 Calibrating the Vacuum Sensor
As the production conditions for the internally integrated vacuum sensor can vary, we recommend cali-
brating the sensor once it is installed in the ejector. To calibrate the vacuum sensor, the system's vacuum
circuit must be open to the atmosphere.
The function for zero-point adjustment of the sensor is performed in the basic menu under the parameter
CAL
or using IO-Link.
1. Press the
button
ð
The menu changes to input
2. Press the
or
button until
cal
appears in the display
3. Confirm with the
button
4. When
YE5
appears, press the
button to confirm.
ð
The vacuum sensor is now calibrated.
A zero offset is only possible in the range of ± 3% around the theoretical zero position.
When the permissible limit is exceeded by ±3%, error code
E03
will appear in the display.