Product Description
EN-US · 30.30.01.02533 · 00 · 11/20
11 / 42
3.5 Function Instuction
3.5.1 Function Setting Mode
Function
Code
Item
Default setting
Explanation
[
F-01
]
[
oVt1
] OUT1 setting
ovt 1
Select Output 1 corre-
sponding to flow sen-
sor or pressure sensor.
Set the flow rate or
pressure value to
switch ON/OFF.
[
oVt1
] OUT1 sensor
correspondence
[
] OUT1 output
mode
xY5
[
ovt1
] OUT1 output
type
no
[
Fl-1
] OUT1 set value
input
50% of maximum measured flow rate
005 : 250 mL/min ' 010 : 500 mL/min
050 : 2.50 L/min ' 100 = 5.00 L/min
500 : 25.0 L/min ' 101 = 50.0 L/min
201 : 100 L/min
[
Fx-1
] OUT1 set value
input
60% of maximum measured flow rate
005 : 300 mL/min ' 010 : 600 mL/min
050 : 3.00 L/min ' 100 = 6.00 L/min
500 : 30.0 L/min ' 101 = 60.0 L/min
201 : 120 L/min
[
F-02
]
[
oVt2
] OUT2 setting
ovt 2
Select Output 2 corre-
sponding to flow sen-
sor or pressure sensor.
Set the flow rate or
pressure value to
switch ON/OFF.
[
oVt2
] OUT2 sensor
correspondence
[
] OUT2 output
mode
xY5
[
ovt2
] OUT2 output
type
no
[
Fl-2
] OUT2 set value
input
50% of maximum measured flow rate
005 : 250 mL/min ' 010 : 500 mL/min
050 : 2.50 L/min ' 100 = 5.00 L/min
500 : 25.0 L/min ' 101 = 50.0 L/min
201 : 100 L/min
[
Fx-2
] OUT2 set value
input
60% of maximum measured flow rate
005 : 300 mL/min ' 010 : 600 mL/min
050 : 3.00 L/min ' 100 = 6.00 L/min
500 : 30.0 L/min ' 101 = 60.0 L/min
201 : 120 L/min
[
F-03
]
[
CLor
] LCD Display set-
ting
Clor
Select back light color
and display mode.
[
di5p
] LCD Display cor-
responding to output
ovt1
[
di5p
] LCD Display
color selection
5og
[
F-04
]
[
rE5P
] Response time
selection
rE5P
Select the response
time for analog out-
put.
Pressure sensor: 2.5ms
~ 1500ms
Flow sensor: 50ms ~
1500ms
[
rE5P
] Flow/Pressure
sensor selection
[
] Response time
selection
800
(ms)