HOW TO USE OPTION CODES 

 

Some accessories and operating functions of the EDI-V5 control require software 
switches to be turned on or off. These switches are called Options and are made 
accessible by the special access code 5996. To change an option, press 5996 

Enter

 

at the 

OPERATING

 screen. The following example screen will appear. 

 
 
 
 
 
 
 
The Ones and Zeros on Line 2  signify which of 16 option switches are on and 

which are off. Starting from the left, Options 1-3 are on, 4-11 are off, 12 is on and 
13-16 are off. Refer to the EDI-V5 OPTIONS chart on the next page to determine 
the action for each switch. 

 
As an example, option 16 turns the motor heater on or off. In the screen above it is 

shown as being off. To turn it on, press 16 

Enter

. The following screen then 

appears showing the present status of this option and requests a 0 or 1 input to 
change it, or 

Enter

 to leave it unchanged. 

 
 
 
 
 
 
 
 
Press 1 (for on) and the first screen will re-appear, showing the change and 

awaiting the selection of another option. Pressing 

Enter

 without entering a number 

will return the control to the O

PERATING

 screen. 

 
Many of the options shown in the chart are used for enabling auxiliary devices to 

the EDI-V5 control. 

Most of these must be used with caution because they can 

adversely affect reliable operation of the distributor. 

Please contact our 

technical support group if you are unsure of how to use these options. 

 

See the chart on the following page for a complete list of options

 

 

   MODIFY OPTIONS  
  1110000000010000                   
OPTION NBR TO CHANGE 

             -> _

      

   MODIFY OPTIONS  
  1110000000010000                   
       HEATER ON=0 

   0=Off, 1=On ->

      

Содержание EDI-V5 CONTROL

Страница 1: ...rter Drive Wiring The Control Configuring The Control Customizing The Display Access Code Description How To Use The Option Codes Screen Alerts And Alarms EDI V5 Accessories For Controls with firmware...

Страница 2: ...to improper operation equipment damage or serious injury or death The EDI control should only be installed and wired by experienced electricians Make sure the wiring meets all applicable regulations...

Страница 3: ...spout Figure 1 shows the field wiring required for the 110 volt supply sensor and motor connections Wire these using the following 3 step procedure Panel Power 110 Volt Wiring Motor Power 230 Volt Wi...

Страница 4: ...sors Refer to Figure 1 and 3 and route the 4 sensor wires into the upper left section of the control box as shown Connect the 4 sensor wires to the screws labeled 1 2 4 and 5 on the barrier relay as s...

Страница 5: ...de cluster on the codewheel passes by See the diagram on the previous page for the location of the switches that manually operate the motor Manually press the Fwd or Rev buttons to begin spout motion...

Страница 6: ...te Some of the information on the sample screens shown may be different than your screen depending on the type of the distributor being installed Upon Power up or Reset the control will display the fo...

Страница 7: ...lm 0 SCHLAGEL INC 002 POSITION 2 _ FLATBACK SWINGSET V5 001 10 DUCTS Dir 0 Slt 5 W 2 27 Upon completion of the Autotune process an information screen will appear with the information it has acquired B...

Страница 8: ...SCHLAGEL INC SCHLAGEL INC EDI V5 CONTROL Page 8...

Страница 9: ...ght These changes are made using special 4 digit access codes The following changes were made to the default OPERATING screen Line 1 The caption on this line has been changed from SCHLAGEL INC to RECE...

Страница 10: ...to 16 characters may be entered A space is entered with a single Shift and Space A backspace can be executed by a double Shift and Space When finished press the Enter key The display will return to th...

Страница 11: ...ers may be entered When finished press the Enter key The display will return to the OPERATING screen showing the new information Hint The position of the distributor can always be moved to the desired...

Страница 12: ...on adjustment numbers for any duct This number will then be used for all spout positions 5993 Define Duct Data Assign Access numbers Function numbers and Names for any duct 5994 Erase Memory Erase all...

Страница 13: ...he screen above it is shown as being off To turn it on press 16 Enter The following screen then appears showing the present status of this option and requests a 0 or 1 input to change it or Enter to l...

Страница 14: ...ete c 0 Off 1 On b 0 6 I O Binary c 0 Off 1 On b 0 7 I O Network d 0 Off 1 On b 0 8 N A 0 9 Auto Mode Speed 0 1 Sec 1 4 Sec 0 10 N A Options 0 11 Simulator Mode 0 Off 1 On 0 12 10 Second Timeout 0 Off...

Страница 15: ...hanical difficulty preventing proper final positioning Remedy This is not a fatal error but the alarm will stay in the screen until a successful position has been achieved To clear the alarm re enter...

Страница 16: ...e module One UCOM is used on each EDI control that will connect to a UIO interface module Remote Keypad Display Kit Remote keypad displays allow operation of an EDI control from multiple locations The...

Отзывы: