15  •  Schlage  •  WRI400 user guide

Credential readers

An input device with either Wiegand (Data1/Data0) or magnetic (clock and data) bit stream 

can be used with the WRI400. The WRI400 provides two separate credential reader 

interfaces.
Connect the shield of the Reader 1 cable to the WRI400 J17-3 terminal (GND). Connect the 

shield of the Reader 2 cable to the WRI400 J18-3 terminal (GND). Do not connect the cable 

shield at the credential reader.

 

L

Reader input ports are designed for 5V logic. Any voltage greater than 5V may 

cause damage to either the WRI400 or the readers.

The WRI400 does not provide power to the readers. Power must be provided to the 

readers separately by a UL listed power supply.
The WRI400 may not provide complete control of the reader’s beeper or LEDs. Please 

consult with your reader’s manufacturer for instruction on reader configuration.

Reader 1 

terminal

Reader 2 

terminal

Description

CLK/D1

J17-1

J18-1

Credential reader inputs: Each input line is pulled to GND 

through a 12V transient suppressor and a 2 mega-ohm 

resistor.
Wiegand or magnetic format is automatically detected.

DATA/D0 J17-2

J18-2

GND

J17-3

J18-3

The signal ground of the WRI400 must be tied to the 

signal ground at the reader.

BEEPER J17-4

J18-4

Beeper signal line connection to the reader.
This is an “open collector” style output and has a 12V 

transient suppressor to GND.
The output is switched to GND through a 100 Ohm 

resistor to activate the beeper on the reader.
NOTE: Most readers beep independently, and beeper 

performance depends on the specific reader model.

GRN

J17-5

J18-5

Green LED signal line connection to the reader.
This is an “open collector” style output and has a 12V 

transient suppressor to GND.
The output is switched to GND through a 100 Ohm 

resistor to activate the green LED on the reader.

RED

J17-6

J18-6

Red LED signal line connection to the reader.
This is an “open collector” style output and has a 12V 

transient suppressor to GND.
The output is switched to GND through a 100 Ohm 

resistor to activate the red LED on the reader.

Содержание WRI400

Страница 1: ...PER STATUS RELAY RX TX USB 12V 5V LID 3 3V RX TX GND OPEN A 1 1 1 1 1 1 1 1 23394075_C SCHLAGE LINK RESET TAMPER GND 20 19 2 1 ICLK IDAT RB8 RB7 GND VDD MCLR USB AA BATT LINE ALR_NC ALR_C ALR_NO AUX A...

Страница 2: ...he WRI400 9 Wiring the WRI400 to access control peripherals 10 WRI400 Cable wire specifications 10 Portal inputs 12 Portal outputs 13 Credential readers 15 Power failure modes 16 Handheld device HHD 1...

Страница 3: ...uipment manufactured and or sold by Allegion LLC is not rated for or intended for use in life safety installations UL listed panic hardware must be used to allow emergency exit from the protected area...

Страница 4: ...e UL listed power sources for the WRI400 and the readers is an acceptable alternative 7 Install the Panel Interface Module PIM400 TD2 or PIM400 485 See the installation guide that came with the PIM or...

Страница 5: ...a Module ANT400 with the PIM400 and choose a location that is free of obstacles which may cause a reduction in signal power at the receiver The distance between the PIM400 and its antenna should not e...

Страница 6: ...n optional remote antenna L L To avoid damage to electronics inside the enclosure when drilling use light pressure so that the bit does not penetrate very far when it breaks through the enclosure or r...

Страница 7: ...e of the building s outer wall nearest the gate Use a remote antenna with the PIM400 and mount the antenna on the outside the building in direct line of sight to the WRI400 s L L If the WRI400 is moun...

Страница 8: ...0 Cabled hoist machine installations with lower machine rooms Use a Remote Antenna Module ANT400 with the PIM400 to prevent contamination of the PIM400 from settled dust oil and debris Hydraulic machi...

Страница 9: ...the bit does not penetrate very far when it breaks through the enclosure or remove electronics from the enclosure before drilling Mounting the WRI400 Follow these steps to permanently attach the WRI40...

Страница 10: ...RI400 enclosure door and generates a tamper trouble signal when the lid is open When terminals J2 1 and J2 2 are shorted a tamper trouble signal is sent to the UL listed access control panel WRI400 Ca...

Страница 11: ...DC THIS MOUNT LED2 BATTERY_HOLDER1 R112 C61 U4 REL1 J3 J7 REL2 REL3 U5 TP25 TP24 TP23 TP22 TP21 J6 LED1 LED4 LED7 LED5 LED6 LED3 J18 J17 J13 LED8 LED9 C32 J9 J12 J11 J10 J8 S3 S2 S1 J5 J2 J1 Ground Re...

Страница 12: ...tatus signal to the ACP Switch closed GND Request to Enter GND J13 3 Ground Electrical ground common for the WRI400 RTX J13 4 Request to exit When the switch opens or closes the WRI400 will send a Req...

Страница 13: ...ption STR_NO J6 1 Strike normally open The strike relay is capable of switching up to a 6 Amp resistive load at 24 VDC 6 Amp at 120 VAC or 3 Amp at 240 VAC STR_C J6 2 Strike common STR_NC J6 3 Strike...

Страница 14: ...onduit as any other WRI400 wiring Connect the shield of the portal output cables to the appropriate earth ground terminal of the electrical lock load or auxiliary load power supply The shield SHOULD N...

Страница 15: ...J18 1 Credential reader inputs Each input line is pulled to GND through a 12V transient suppressor and a 2 mega ohm resistor Wiegand or magnetic format is automatically detected DATA D0 J17 2 J18 2 G...

Страница 16: ...effect For the system to fail secure the secure mechanism must be tied to the normally closed side For fail secure UL listed panic hardware must be used to allow emergency exit from the protected are...

Страница 17: ...LED7 LED5 LED6 LED3 J18 J17 J13 LED8 LED9 C32 J9 J12 J11 J10 J8 S3 S2 S1 J5 J2 J1 J5 USB L L The WRI400 is communicating with the HHD when the USB LED blinks green and the HHD display indicates WRI40...

Страница 18: ...ed and the WRI400 must be linked to the PIM400 Link the WRI400 to a PIM400 The WRI400 and PIM400 must be linked for programmed credentials to function L L Make sure the PIM400 is in link mode Refer to...

Страница 19: ...utton Test will not result in the loss of any WRI400 settings or programming changes 1 While holding the Schlage button press and release the reset button 2 All relays on board LEDs reader LEDs and re...

Страница 20: ...red blinks from the RX TX is normal for an unauthorized card The credential reader is not operating properly The WRI400 STRIKE Relay LED is not activated when a card or keypad credential is presented...

Страница 21: ...access control panel Aux relay action is assigned by the access control panel A credential must have aux relay rights before the ACP will command the WRI400 to activate the aux relay The aux relay wil...

Страница 22: ...valid credential to the reader within 5 secs If the credential is not presented within 5 seconds time out will occur Note WRI400 must be in factory default state to program the master construction cre...

Страница 23: ...ency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communication However there is no guarantee that interference will not occur in a...

Страница 24: ...Antennas having a gain greater than the antenna type approved in the list are strictly prohibited for use with this device However antennas of the same type with a gain equal to or less may be used Ex...

Отзывы: