To change from operation to parametrisation mode push
"enter button" for minimum 3 seconds. Back over the
menu save and exit.
Language
English
Range
0...+50 °C, 0...100 % rH
Output
each 0…10 VDC, 0…20 mA
Outputs Ex-i
4…20 mA
Parametrisation and commissioning of ExCos-D (-A) transducers after an ExPro-C... sensor ist connected
Change operation-/parametrisation mode Example of parameters
Menu 1
DE, EN, FR
english
Menu 2
unit sensor 1
°C
range 1
0
..50 °C
range 1
0..
50 °C
output V/mA
V
output range 1
0
..10V
sensor error 1
10V / 20 mA
output 1
increasing
output Exi 1
4
..20 mA
output Exi 1
4..
20 mA
no function - menu skip
DE, EN, FR
select language: German, English, French
Menu 3
no function - menu skip
Menu 4 unit sensor 1
select physical unit
°C, °F
deutsch, english, francais
Menu 5 range 1
adjust the measuring range
adjust lower limit
adjust higher limit
Menu 6
no function - menu skip
Menu 7 output V, mA
select output signal as VDC or mA
mA, V
Menu 8 output range 1
adjust the output range
adjust lower limit
adjust higher limit
output range 1
0..
10V
Menu 9 sensor error 1
select signal at sensor error
10V / 20 mA or 0V / 0mA
Menu 10 output 1
select if signal output is increasing or decreasing
increasing, decreasing
Menu 11 unit sensor 2*
select physical unit
Menu 12
Menu 13
Menu 14
Menu 15
Menu 16 output Ex-i 1 (option, only at ExCos-D-A)
adjust 4...20 mA or 0...20 mA IS output signal
Menu 17
Menu 18
Menu 19 display function
select display on/off, illuminated or backlight off
Menu 20 password
select password protection
Menu 21 save and exit
select save data / factory setting / discard
or back to menu
Menu
Indication
Function
Select
Enter
Next selsction
Enter
Next menu
Next indication
Enter
display function
on illuminated
new password
yes no
save and exit
save data
unit sensor 2
%rH
%rF, %rH
range 2
0
..100 %rH
range 2
0..
100 %rH
range 2*
adjust the measuring range
adjust lower limit
adjust higher limit
output range 2
0
..10V
output range 2*
adjust the output range
adjust lower limit
output range 2
0..
10V
adjust higher limit
sensor error 2
0V / 0 mA
sensor error 2*
select signal at sensor error
10V / 20 mA or 0V / 0mA
output 2
increasing
output 2*
select if signal output is increasing or decreasing
increasing, decreasing
output Exi 2
4
..20 mA
output Exi 2
4..
20 mA
output Ex-i 2 (option, only at ExCos-D-A)*
adjust 4...20 mA or 0...20 mA IS output signal
no function - menu skip
Menu 22 Set offset 1
Add / subtract from measures value
Menu 23 Set offset 2 *
Add / subtract from measures value
set offset 1
0.00°C
sett offset.2
0.00%rH
password
0000
on-illuminated, on, off
adjust lower limit
adjust lower limit
adjust higher limit
adjust higher limit
*
only available if combination sensor type ExPro-CTF... is connected
Operation
Parametrisation, push for 3 sec.
If password (PW) protection is active: put PW in, push
Preparation of parametrisation/operation