background image

Schischek GmbH 

Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail [email protected]

www.schischek.com

E X P L O S I O N P R O O F

ExCos-D... transducer

ExPro-C... sensor 

Example: room sensor

Example: duct sensor

ExCos-D...-CT 

Shown:

ExPro-...-CTF…

Description

Application

Highlights transducer

Transducer

Connectable sensors (compulsory for ExCos-D... transducer) – see separate data sheet

Highlights sensor

Electrical, explosionproof transducers only connectable to 

ExPro-C...

 

temperature and humidity sensors. 

24 VAC/DC supply, 0…10 V / (0)4…20 mA output 

PTB-certified in acc. with ATEX directive 94/9/EC for zone 1, 2, 21, 22.

 For all type of gas, mixtures, vapours and dust for use in zone 1, 2, 21 and 22

 No addional Ex-i module required

 No intrisically safe wiring/installation between panel and sensor required

 No intrisically safe wiring/installation and no space in the panel required

 Integrated Ex-e junction box

 Power supply 24 VAC/DC

 Display with backlight, can be switched off

 Scalable analogue output, selectable 0…10 V / (0)4…20 mA

 Compact design and small dimension  (L × W × H = 180 × 107 × 66 mm) 

 Robust aluminium housing in protection class IP66

 Down to –20°C ambient temperature applicable

 Password locking

 Optional IS-output (0)4…20 mA for external indicator in Ex-areas

 CT versions have an excellent resistance to chemicals and seawater

 For all type of gas, mixtures, vapours and dust for use in zone 1, 2, 21 and 22

 Plug-and-socket connection to ExCos-D... transducer, removable

 The ExPro-C... probe appropriates the function (temperature, humidity or combination)

 Mounting of ExPro-C... probe (front/back side) appropriates use for duct or room application 

ExCos-D

  

Transducer for ExPro-C... sensors (probes)

ExPro-C... 

Temperature/humidity sensors (°C, %rH)

1 / 4

The 

ExCos-D...

 transducer generation from together with direct coupled 

ExPro-C... sensors

 are a revolution for measuring temperature and/or 

humidity in HVAC systems,  in chemical, pharmaceutical, industrial and 
Offshore-/Onshore plants, for use in hazardous areas zone 1, 2 (gas) 
and zone  21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimension, 
universal functions and technical data guarantee safe operation even 
under difficult environmental conditions. 
The measuring ranges are scalable within the maxium ranges. The 
analogue output signal is either 0...10 VDC or (0)4...20 mA and can be 
selected on site. The integrated display is for actual value indication 
which can be switched off.
All sensors are programmable on site without any additional tools.

ExCos-D-A

 transducer are additionally equipped with a (0)4…20 mA IS 

(IS = intrinsically safe) output, e.g. for an external indicator.

Subject to change!

Type of transducer:

ExCos - D

ExCos - D - A

ExCos - D... - CT

Type of sensor (probe):

ExPro - CT...

ExPro - CF...

ExPro - CTF...

Type 

Supply 

Installation area  Connectable sensors 

 

Function of sensors  

Sensor connection 

Wiring diagram

ExCos - D 

24 VAC/DC  zone 1, 2, 21, 22  ExPro-CT..., ExPro-CF..., ExPro-CTF... 

°C, % rH, combination °C/% rH  via plug-and-socket connection  SB 2.0

ExCos - D - A 

as above, but with additional intrisically safe analogue output to connect an external digital indicator (0)4...20 mA (Ex-i) 

 

SB 3.0

ExCos - D...- CT 

Type as above but with aluminium housing and Amercoat painting (sensor connection cable glands nickel-plated, screws in stainless steel)

Type 

Function  

Measuring range 

Length of sensor 

connectable to  

Installation sensor  Installation transducer

ExPro - CT… 

temperature 

–40...+125 °C* 

50/100/150/200 mm  ExCos-D..., RedCos-D...  zone 1, 2, 21, 22 

zone 1, 2, 21, 22 (ExCos…)

ExPro - CF… 

humidity 

    0...100 % rH 

50/100/150/200 mm  ExCos-D..., RedCos-D...  zone 1, 2, 21, 22 

zone 1, 2, 21, 22 (ExCos…)

ExPro - CTF… 

combination temp./humidity  –40...+125 °C*/0...100 %rH  50/100/150/200 mm  ExCos-D..., RedCos-D...  zone 1, 2, 21, 22 

zone 1, 2, 21, 22 (ExCos…)

  

* at 50 mm length –40…

+80

 °C

sensor length

Содержание ExPro-CTF Series

Страница 1: ...xCos D transducer generation from together with direct coupled ExPro C sensors are a revolution for measuring temperature and or humidity in HVAC systems in chemical pharmaceutical industrial and Offshore Onshore plants for use in hazardous areas zone 1 2 gas and zone 21 22 dust Highest protection class ATEX and IP66 protection small dimension universal functions and technical data guarantee safe ...

Страница 2: ...end value accuracy of ExPro C sensor 0 3 C at 25 C 0 025 C C Accuracy humidity 0 2 of end value accuracy of ExPro C sensor 10 90 rH 2 and 10 rH and 90 rH 4 1 hysteresis Non linearity and hysteresis 0 1 of end value Start delay 5 s Stability long term stability 0 2 year temperature influence 0 02 K supply voltage influence 0 01 Output voltage U V or current I mA selecable via menu on site at combi ...

Страница 3: ...ly one sensor to one transducer In acc with the sensor type you need to set parameter for one or two measuring ranges Wiring diagram ExCos D Values intrinsically safe IS for ExPro C sensors Password input Parameter Wiring Ex i output optional at ExCos D A transducer Important information for installation and operation A Installation commissioning maintenance The cable has to be drawn through the c...

Страница 4: ...reasing decreasing Menu 11 unit sensor 2 select physical unit Menu 12 Menu 13 Menu 14 Menu 15 Menu 16 output Ex i 1 option only at ExCos D A adjust 4 20 mA or 0 20 mA IS output signal Menu 17 Menu 18 Menu 19 display function select display on off illuminated or backlight off Menu 20 password select password protection Menu 21 save and exit select save data factory setting discard or back to menu M...

Отзывы: