E X P L O S I O N P R O O F

In acc. to the connected 

ExPro-C... 

sensor

 you get output signals at 

following terminal:

sensor 

terminal terminal

ExPro-CT... 

3 - 4

ExPro-CF... 

 

4 - 5

ExPro-CTF...  3 - 4   und  4 - 5

It's either output mA or V adjustable.

Attention !

Humidity output below 0 °C no 

function

ExCos-D...

SB 2.0

The ExPro-C... probe can be mounted to 

the front or the back side of the transducer.

The protective cap must be removed.

Unused connectors must be covered by a 

protective cap against mechanical damage 

and dirt.

Values IS (optional)

Uo =  15,8 V

Io   =  85 mA

Po  =  336 mW

Ci   =  0

Li   =  0

Co(IIC) = 0,33 nF

Lo(IIC)  = 2 mH

Terminals

SB 3.0

Head side of ExCos-D-A sensor

Connector  1 for output of sensor 1 (°C)

Connector  2 for output of sensor 2 (%rH)

Push button

ENTER

Display for 

programming and 

indication

Push button

for level select

Uo =  7,9 V

Io   =  48 mA

Po  =  95 mW

Ci   =  0

Li   =  0

Co(IIC) = 1,3 nF

Lo(IIC)  = 2 mH

Digital ExPro-C... sensor

to connect e.g.

an external  LCD indicator

 

4 1

2

5

3

Male connector

 

1

2

4

3

Female connector

 

Dimensions / Drillings

PA

1

2

3

4

~

~

+

24 VAC/DC

PE

(0)4…20 mA

0…10 V

GND

°C /% rH

5

(0)4…20 mA

0…10 V

°C

% rH

E X P L O S I O N P R O O F

Ø ExPro

68

157,5

117

129

166

80

107

55

66

~ 180

20

– +

3 / 4

ExCos-D...

Electrical wiring

The default/delievery setup is 

0000

. In this configuration the password input is not 

activated. To activate a password, go to menu point 20, change the 4 digits into your 

choosen numbers (e.g. 1234) and press Enter. 

Please keep your password in mind for next parameter change!

 

Due to a new parameter setup the password is requested. 

Before starting parametrisation of 

ExCos-D... 

transducer an 

ExPro-C... 

sensor must be 

connected. ExPro-C... sensors are available as ExPro-CT... for single temperature measure-

ment, as ExPro-CF... for single humidity measurement and as ExPro-CTF... for combined 

measurement of temperature and humidity. All types are connectable to an ExCos transducer 

but only one sensor to one transducer. In acc. with the sensor type you need to set parameter 

for one or two measuring ranges.  

Wiring diagram  ExCos-D...

Values intrinsically safe (IS) for ExPro-C... sensors

Password input

Parameter

Wiring  

Ex-i output (optional) at ExCos-D-...A transducer

Important information for installation and operation

A. Installation, commissioning, maintenance

The cable has to be drawn through the cable gland. After electrical connection the 

cable gland must be fixed tighten. IP66 must be fulfilled.

In acc. with operation ExCos sensors are maintenance free. Nevertheless maintenance 

must comply with regional standards, rules and regulations.  

The sensors must not be opened by the customer. For outdoor installation a protective 

housing against rain, snow and sun should be applied. For electrical connection use 

the internal approved Ex-e junction box. 

Attention:

 Note the explosion proof rules before opening the internal junction box. 

Cut off the power supply.

B. ExPro-C... sensors

ExPro-C... sensors are supplied with an instrinsically safe circuit from the ExCos-D... 

transducer. Unused connectors must be covered by a protective cap.

C. Long cabling

For using long signal wires, shilded cables are recommended. The shield must be 

connected to the ExCos-D transducer inside the terminal box.

D. Separate ground wires

Use for supply and signal wires a separate ground.

ExCos-D...

 transducer require a 24 VAC/DC power supply

.

 The supply has to be connected at 

terminal 1 (–/~) and 2 (+/~), the analogue output at terminal 3 (mA/V) and 4 (GND) for 

temperature, at terminal 5 (mA/V) and 4 (GND) for humidity. The electrical wiring must be realized 

via integrated Ex-e junction box in acc. to ATEX. Type of protection for the terminals is "Ex-e".  

Attention!

 Before opening the junction box cover,  the supply voltage must be shut off!

The optional analogue output at 

ExCos-D-A

 is intrinsically safe. Note the maximum connection 

values of intrinsically safe parameters (see table below). 

Display and Buttons

To change from operation to parametrisation mode and vice versa, push the enter button 

        for minimum 3 seconds. 

A blinking star in the display shows that data is received and the device is working.

Change operation-/parametrisation mode

Indication of data logging

Содержание ExPro-CTF Series

Страница 1: ...xCos D transducer generation from together with direct coupled ExPro C sensors are a revolution for measuring temperature and or humidity in HVAC systems in chemical pharmaceutical industrial and Offshore Onshore plants for use in hazardous areas zone 1 2 gas and zone 21 22 dust Highest protection class ATEX and IP66 protection small dimension universal functions and technical data guarantee safe ...

Страница 2: ...end value accuracy of ExPro C sensor 0 3 C at 25 C 0 025 C C Accuracy humidity 0 2 of end value accuracy of ExPro C sensor 10 90 rH 2 and 10 rH and 90 rH 4 1 hysteresis Non linearity and hysteresis 0 1 of end value Start delay 5 s Stability long term stability 0 2 year temperature influence 0 02 K supply voltage influence 0 01 Output voltage U V or current I mA selecable via menu on site at combi ...

Страница 3: ...ly one sensor to one transducer In acc with the sensor type you need to set parameter for one or two measuring ranges Wiring diagram ExCos D Values intrinsically safe IS for ExPro C sensors Password input Parameter Wiring Ex i output optional at ExCos D A transducer Important information for installation and operation A Installation commissioning maintenance The cable has to be drawn through the c...

Страница 4: ...reasing decreasing Menu 11 unit sensor 2 select physical unit Menu 12 Menu 13 Menu 14 Menu 15 Menu 16 output Ex i 1 option only at ExCos D A adjust 4 20 mA or 0 20 mA IS output signal Menu 17 Menu 18 Menu 19 display function select display on off illuminated or backlight off Menu 20 password select password protection Menu 21 save and exit select save data factory setting discard or back to menu M...

Отзывы: